Basler Electric BE1-700 User Manual

Page 85

Advertising
background image

Table 4-17. Operating Settings for Phase Undervoltage/Overvoltage Protection

Setting

Range

Increment

Unit of Measure

Default

Pickup

0 = Disabled

10 to 300

0.1 for 0 to 99.9

1.0 for 100 to 300

Secondary Volts †

0

Inhibit

27 only

0 = Disabled

10 to 300

0.1

Secondary Volts †

0

Time Delay

50 to 999 milliseconds

1

Milliseconds

50 ms

1 to 600 seconds

0.1 for 1.0 to 9.9

Seconds

1.0 for 10 to 600

Seconds

3 to 36,000 cycles (60 Hz)

Cycles

2.5 to 30,000 cycles (50 Hz)

∗ Time delays less than 10 cycles can be entered to the nearest 0.1 cycles from the front panel HMI. All
time delays can be entered to the nearest 0.01 cycles from the ASCII command interface. Time delays
entered in cycles are converted to milliseconds or seconds. Increment precision after conversion is
limited to that appropriate for each of those units of measure.

† Unit of measure is secondary VPP or secondary VPN depending on the VTP connection settings.

Time delay settings entered in cycles are converted to seconds or milliseconds (per the nominal
frequency setting stored in EEPROM) before being stored. See Section 3, Input and Output Functions,
Power System Inputs
, Voltage Measurement, for more information about this setting. If the nominal
frequency setting is being changed from the default (60 hertz) and time delay settings are being set in
cycles, the frequency setting should be entered and saved before making any time delay settings
changes.

Retrieving Phase Undervoltage/Overvoltage Protection Status from the Relay

The status of each logic variable can be determined through the ASCII command interface using the RG-
STAT (report general-status) command. See Section 6, Reporting and Alarm Functions, General Status
Reporting
, for more information. The status can also be determined using BESTCOMS Metering screen.

27X/59X - Auxiliary Undervoltage/Overvoltage Protection

Figure 4-25 illustrates the inputs and outputs of the auxiliary under/overvoltage elements. Element
operation is described in the following paragraphs.

Figure 4-25. Auxiliary Undervoltage/Overvoltage Logic Blocks

The auxiliary elements have two outputs: 27/59XPU (pickup) and 27/59XT (trip). When the monitored
voltage increases above the pickup setting, the pickup output becomes TRUE and the element starts
timing toward a trip. The trip output becomes TRUE when the element timer times out.

The BLK (Block) input is used to disable protection. A BESTlogic expression defines how the BLK input
functions. When this expression is TRUE, the element is disabled by forcing the outputs to logic 0 and
resetting the timer. This feature functions in a similar way to the torque control contact of an
electromechanical relay.

D2871-21

05/13/02

159XT

159XPU

BLK

159X

Mode

BLK

27XT

27XPU

AUX

UNDER-

VOLTAGE

(27X)

Mode
0-Disable
1-Fundamental Vx Input
2-3VO - 3ph VT Input
3-Harmonic Vx Input

BLK

59XT

59XPU

AUX

OVER-

VOLTAGE

(59X)

Mode

0-Disable
1-Fundamental Vx Input
2-3VO - 3ph VT Input
3-Harmonic Vx Input

9376700990 Rev M

BE1-700 Protection and Control

4-29

Advertising
This manual is related to the following products: