Basler Electric BE1-700 User Manual

Page 203

Advertising
background image

Function

Purpose

BESTlogic

Expression

Mode Setting

381

Overfrequency Protection Level 2

0

1

(Phase VT input)

481

Overfrequency Protection Level 1

0

1

(Phase VT input)

581

Overfrequency Protection Level 2

0

1

(Phase VT input)

GROUP

Input 0 Logic: No manual selection logic is used

0

1

(discrete input

selection)

Input 1 Logic: No manual selection logic is used

0

Auto/Manual Logic: Set to 1 (/0) to enable automatic
selection. Manual selection is not used.

/0

Table 8-13. 700V-OUVF-A-BE (Over/Under V & F Protection) Virtual Switch Logic

Switch

Purpose

Mode

Label

State Labels

Closed

Open

43

Not used

0 (disabled)

SWITCH_43

Closed

Open

143

Not used

0 (disabled)

SWITCH_143

Closed

Open

101

Not used

0 (disabled)

N/A

N/A

N/A

Table 8-14. 700V-OUVF-A-BE (Over/Under V & F Protection) Virtual Output Logic

Output

Purpose

Description

Label

State Labels

Closed

Open

VOA
(OUTA)

Relay Trouble alarm, Alarm
Major, Alarm Minor

OUTA contact closes when
Relay Trouble, Major or
Minor alarm is TRUE

RELAY_TR

Active

Normal

BESTlogic expression: VOA= ALMMAJ+ALMMIN

VO1
(OUT1)

Not used

VO1

True

False

BESTlogic expression: VO1=0

VO2
(OUT2)

Breaker Trip Contact
initiated by Voltage and
Frequency Trips

OUT2 contact closes if any
voltage (24, 27P, 127P,
27X, 47, 59P, 159P, 59X,
159X) or frequency
(81

Y581) trip is TRUE.

V&F_BKR_TR

Trip

Normal

9376700990 Rev M

BE1-700 Application

8-21