Links between programmable alarms and bestlogic, Figure 6-22. alarm reset logic -31, Figure 6-23. alarms status, metering screen -31 – Basler Electric BE1-700 User Manual

Page 163: Ee figure 6-22, Figure 6-22, Alarm reset logic

Advertising
background image

Figure 6-22. Alarm Reset Logic

The Reset key of the HMI is context sensitive. That is, the functionality depends upon what screen is
currently being displayed. BESTlogic variable ARSTKEY takes advantage of this to allow the front panel
Reset key to be used in the programmable logic scheme when Alarms screen 1.3 is active. An example of
the use of this logic variable is to break the seal-in for a logic expression. The logic expression can be
programmed so that the seal-in function uses VO13, VO14, or VO15. If the virtual output expression is
included in one of the programmable alarm masks, the automatic display priority logic will cause the
display to go to Alarms screen 1.3. When the HMI Reset key is pressed, the ARSTKEY logic variable is
asserted and the logic expression seal-in is broken. See Section 8, Application, Application Tips, for more
information. Pressing the HMI Reset key while the Alarms screen is displayed, will clear any latched
alarms that are not currently active. Refer to Table 6-17 for a list of latching alarm points and self-clearing
alarm points.

After an operation, alarms information can be viewed using BESTCOMS. Select Metering from the
Reports pull-down menu. From the View pull-down menu, select Alarms Status (Figure 6-23).

Figure 6-23. Alarms Status, Metering Screen

The RA (report alarms) command can be used to read detailed alarm reports and reset latched alarms.

Links between Programmable Alarms and BESTlogic

Several links between the programmable alarms and BESTlogic allow alarm functions to be used in the
logic scheme and programmable logic functions to be used in the alarm reporting function.

Programmable Alarms Controlled by BESTlogic Elements

Virtual Outputs VO13, VO14, and VO15 are driven by BESTlogic expressions and are available in the
programmable alarms function. These three virtual outputs have labels that can be assigned meaningful
names. Then, when a logic condition that is used for an alarm exists, the label will be reported in the
alarm reporting function.

Programmable Alarms Reset

Programmable alarms can be reset by any one of three methods:

• The programmable alarms reset logic expression becomes TRUE.
• Pressing the front panel Reset key when HMI Screen 1.3 is active.
• Connecting the alarms reset logic in BESTCOMS. Alternately, this can be done using the SA-

RESET ASCII command.

D2850-09.vsd

06-29-99

RA-MAJ=0

Logic

Alarm
Reset

Logic

RA-MIN=0

ARSTKEY

HMI RESET KEY

9376700990 Rev M

BE1-700 Reporting and Alarm Functions