Table 13-86. x62 mode 2 test commands -47 – Basler Electric BE1-700 User Manual

Page 343

Advertising
background image

Table 13-84. x62 Mode 1 Timer Initiate Commands

Command

Purpose

A=

Gains write access.

CS-43=1

Selects 43 for On operation.

CO-43=1

Executes 43 for On operation.

Step 4: Transmit the commands in Table 13-85 to the relay. These commands will remove the initiate

input from the 62 Timer by changing the 43 Switch state to open (logic 0).

Table 13-85. x62 Mode 1 Timer Initiate Removal Commands

Command

Purpose

A=

Gains write access.

CS-43=0

Selects 43 for Off operation.

CO-43=0

Executes 43 for Off operation.

Step 5: Use the RS-LGC command to retrieve logic variable data from the SER. Verify that the 43

Switch change to a closed state was logged and approximately 400 milliseconds later, the 62
Timer picked up. Later the 43 Switch change to an open state was logged and the 62 Timer
dropped out approximately 2,000 milliseconds later. The state of the 43 switches in the SER
report use the programmable name parameters applied to the switch. Figure 13-1 illustrates the
timing relationship of the 43 Switch and 62 Timer.

Figure 13-1. x62 Mode 1 (Pickup/Dropout) Timing Example

Mode 2 - One-Shot Nonretriggerable

Step 1: Prepare the 162 Timer for Mode 2 testing by transmitting the commands in Table 13-86 to the

relay.

Table 13-86. x62 Mode 2 Test Commands

Command

Purpose

A=

Gains write access.

SL-N=NONE

Zero out custom logic settings. Overwrite with LOGIC=NONE
settings.

Y

Confirm overwrite.

SL-N=T162

Sets T162 as custom logic name.

SL-162=2,143,0

Enables 162 1-shot, nonretriggerable mode, 143 initiate, no blocking.

SL-143=3

Enables 143 Switch momentary pulse mode.

SN-143=162_INI,INI,NORMAL Name Switch 143 to make SER report easier to read.

9376700990 Rev M

BE1-700 Testing and Maintenance