Function

Purpose

BESTlogic

Expression

Mode Setting

50TQ

Used for instantaneous negative-sequence overcurrent
protection.

0

1 (enabled)

150TP

Not used

0

0 (disabled)

150TN

Not used

0

0 (disabled)

150TQ

Not used

0

0 (disabled)

51P

Used for timed phase-overcurrent protection.

0

1 (enabled)

51N

Used for timed neutral-overcurrent protection

0

1 (3-phase

Residual)

51Q

Used for timed negative-sequence overcurrent protection.

0

1 (enabled)

151N

Not used

0

0 (disabled)

62

Not used

0

0 (disabled)

162

Not used

0

0 (disabled)

BF

Not used

0

0 (disabled)

GROUP

Input 0 Logic: No manual selection logic is used.

0

1

(discrete input

selection)

Input 1 Logic: No manual selection logic is used.

0

Auto/Manual Logic: Set to 1 (/0) to enable automatic
selection. No manual selection is used.

/0

Table 8-3. 700C-5051-A-BE (Basic OC) Virtual Switch Logic

Switch

Purpose

Mode

Label

State Labels

TRUE

FALSE

43

Not used

0 (disabled)

SWITCH_43

CLOSED

OPEN

143

Not used

0 (disabled)

SWITCH_143

CLOSED

OPEN

8-6

BE1-700 Application

9376700990 Rev M