Basler Electric BE1-700 User Manual

Page 202

Advertising
background image

Table 8-11. 700V-OUVF-A-BE (Over/Under V & F Protection) Contact Sensing Input Logic

Input

Purpose

Label

State Labels

Energized

De-Energized

IN1

Breaker status indication in Sequence of
Events Reporting. TRUE when breaker is
open. Typically, IN1 is connected to the 52b
contact of the breaker.

BREAKER

Open

Closed

IN2

Not used

INPUT_2

Closed

Open

IN3

Not used

INPUT_3

Closed

Open

IN4

Not used

INPUT_4

Closed

Open

Table 8-12. 700V-OUVF-A-BE (Over/Under V & F Protection) Function Block Logic

Function

Purpose

BESTlogic

Expression

Mode Setting

24

Used for detection of transformer overexcitation

0

1 (enabled)

27P

Used for phase undervoltage protection Level 1

0

1 (1 of 3)

127P

Used for phase undervoltage protection Level 2

0

1 (1 of 3)

27X

Not used

0

0

47

Used for negative-sequence protection

0

1 (enabled)

59P

Used for phase overvoltage protection Level 1

0

1 (1 of 3)

159P

Used for phase overvoltage protection Level 2

0

1 (1 of 3)

59X

Used for 3Vo voltage detection Level 1

0

2

(3Vo-3 Ph VT input)

159X

Used for 3Vo voltage detection Level 2

0

2

(3Vo-3 Ph VT input)

62/162

Not used

0

0

81

Underfrequency Protection Level 1

0

1

(Phase VT input)

281

Underfrequency Protection Level 1

0

1

(Phase VT input)

8-20

BE1-700 Application