Virtual breaker control switch (101), Virtual breaker control switch (101) -45, Table 13-78. x43 mode 3 pulse commands -45 – Basler Electric BE1-700 User Manual

Page 341

Advertising
background image

Step 2: Prepare to monitor the virtual switch operation. An ohmmeter or continuity tester may be used

to monitor the contact status of OUT1.

Step 3: Transmit the commands in Table 13-78 to the relay. These commands pulse the 143 Switch On

and Off once. Result: OUT1 contact closes for 200 milliseconds and returns to the open state.

Table 13-78. x43 Mode 3 Pulse Commands

Command

Purpose

A=

Gains write access.

CS-143=P

Selects 143 for Pulse operation.

CO-143=P

Executes 143 for Pulse operation.

Virtual Breaker Control Switch (101)

Purpose: To verify 101 Virtual Breaker Control Switch operation.

Reference Commands: SL-101, CS/CO-101C, CS/CO-101T

Step 1: Prepare the 101 Virtual Breaker Control Switch for testing by transmitting the commands in

Table 13-79 to the relay.

Table 13-79. 101 Virtual Breaker Control Switch Test Commands

Command

Purpose

A=

Gains write access.

SL-N=NONE

Zero out custom logic settings. Overwrite with LOGIC=NONE settings.

Y

Confirm overwrite.

SL-N=S101

Sets S101 as custom logic name.

SL-101=1

Enables 101 Switch.

SL-VO1=101T

Enables OUT1 to close when 101T is TRUE.

SL-VO2=101C

Enables OUT2 to close when 101C is TRUE.

SL-VO3=101SC

Enables OUT3 to close when 101SC is TRUE.

EXIT;Y

Exit and save settings.

Step 2: Prepare to monitor the 101 Virtual Breaker Control Switch operation. Operation can be verified

by monitoring the programmed output contacts, HMI Screen 2.2.1 or by using RG-STAT
command. See Section 6, Reporting and Alarm Functions, for more information.

Step 3: Transmit the commands in Table 13-80 to the relay. These commands place the 101 Switch in

the trip position. Result: OUT1 closes for 200 milliseconds and returns to the open state. OUT3
opens (trip state) and remains open.

Table 13-80. 101 Virtual Breaker Control Switch Trip Test Commands

Command

Purpose

A=

Gains write access.

CS-101T=T

Selects 101T for Trip operation.

CO-101T=T

Executes 101T for Trip operation.

Step 4: Transmit the commands in Table 13-81 to the relay. These commands place the 101 Switch in

the closed state. Result: OUT2 closes for 200 milliseconds and returns to the open state. OUT3
closes (close state) and remains closed.

9376700990 Rev M

BE1-700 Testing and Maintenance

13-45

Advertising
This manual is related to the following products: