Settings example for overexcitation protection -24, Figure 4-18. time shown on vertical axis -24, Figure 4-19. time shown on horizontal axis -24 – Basler Electric BE1-700 User Manual

Page 80

Advertising
background image

Table 4-15. Programmable Alarm Settings for Overexcitation Protection

Setting

Range

Increment

Unit of Measure

Default

Alarm Level

0.5 - 6

0.1

Sec. V/Hz

0

Alarm Time Delay

0.050 – 600

3 digit resolution

Seconds

0

Settings Example for Overexcitation Protection

V/Hz tripping elements are used to de-energize a generator or transformer that is experiencing an
overexcitation condition. Therefore, the manufacturer's overexcitation limit curves are required to
establish optimum protection. Figure 4-18 and Figure 4-19 show examples of a transformer and generator
limit curve along with the optimum composite protection characteristic.

Figure 4-18. Time Shown on Vertical Axis

Figure 4-19. Time Shown on Horizontal Axis

Volt/Hz Characteristic

1.0

10.0

100.0

1000.0

100%

105%

110%

115%

120%

125%

130%

135%

140%

Percent of Nominal V/Hz

T

im

e

in

S

e

c

o

n

d

s

Transformer Limit

Generator Limit

Inverse
105%, TD=1.9

Definite
118%, 6s

Volt/Hz Characteristic

100%

105%

110%

115%

120%

125%

130%

135%

140%

1.0

10.0

100.0

1000.0

Time in Seconds

P

e

rc

e

n

t

o

f

N

o

m

in

a

l

V

/H

z

Transformer Limit

Generator Limit

Inverse
105%, TD=1.9

Definite
118%, 6s

D2871-43
02-12-04

NOTE

Actual damage curves must be obtained from the equipment manufacturer for
particular equipment to be protected.

4-24

BE1-700 Protection and Control

9376700990 Rev M

Advertising
This manual is related to the following products: