Basler Electric BE1-700 User Manual

Page 209

Advertising
background image

Function

Purpose

BESTlogic

Expression

Mode Setting

27P

Used for phase undervoltage protection Level 1

0

1 (1 of 3)

127P

Used for phase undervoltage protection Level 2

0

1 (1 of 3)

27X

Not used

0

0

47

Used for negative-sequence voltage protection

0

1 (enabled)

59P

Used for phase overvoltage protection Level 1

0

1 (1 of 3)

159P

Used for phase overvoltage protection Level 2

0

1 (1 of 3)

59X

Used for 3Vo voltage detection Level 1

0

2

(3V0-3Ph VT Input)

159X

Used for 3Vo voltage detection Level 2

0

2

(3V0-3Ph VT Input)

62/162

Not used

0

0

79

Reclose Initiate: Initiates reclosing sequence when
RI is TRUE.

Breaker Status Logic: Closed breaker is indicated
when IN1 is de-energized.

Wait Logic: Stop recloser timing when timing for a
fault trip. TRUE when protection picked up
expression is TRUE.

Block/Drive to Lockout Logic: Drive recloser to
lockout when external recloser on/off switch is off.

Pilot Initiate: Initiate one high speed reclose when PI
is TRUE

VO14

/IN1

VO12

/IN2

VO13

1

(Power Up to Lockout)

81

Underfrequency Protection Level 1

0

1

(Phase VT Input)

281

Underfrequency Protection Level 1

0

1

(Phase VT Input)

381

Overfrequency Protection Level 2

0

1

(Phase VT Input)

481

Overfrequency Protection Level 1

0

1

(Phase VT Input)

581

Overfrequency Protection Level 2

0

1

(Phase VT Input)

9376700990 Rev M

BE1-700 Application

8-27