Output

Purpose

Description

Label

State Labels

VO6

Not used

VO6

True

False

BESTlogic expression: VO6=0

VO7

Not used

VO7

True

False

BESTlogic expression: VO7=0

VO8

Not used

VO8

True

False

BESTlogic expression: VO8=0

VO9

Sync-Check Close

79C is TRUE and 25 is
TRUE

SYNC_

CLOSE

Close

Normal

BESTlogic expression: VO9=79C*25

VO10

Conditional Voltage Close

79C is TRUE and 25VM1
is TRUE

VOLT_

CLOSE

Close

Normal

BESTlogic expression: VO10=79C*25VM1

VO11

Protective trip expression

VO11 is TRUE when any
OC&P or V&F protection
element trips

PROT_TRIP

Trip

Normal

BESTlogic expression:
VO11=24T+27XT+27PT+127PT+47T+59PT+159PT+59XT+159XT+81T+181T+281T+381T+481T+581T

VO12

Protective pickup
expression

VO12 is TRUE when any
protection element picks up

PROT_PU

PU

Normal

BESTlogic expression: VO12=24PPU+27XPU+27PPU+127PPU+47PU+59PPU+159PPU+59XPU +159XPU +81T
+181T +281T+381T+481T+581T

VO13

Pilot Reclose Initiate

VO13 is TRUE when IN1,
is TRUE

PILOT_INI

INI

Normal

BESTlogic expression: VO13=IN1

VO14

Reclose Initiate

VO14 is TRUE when IN3
or VO13 is TRUE

REC_INI

INI

Normal

BESTlogic expression: VO14=IN3+VO13

VO15

Alarm Mask 21

VO15

True

False

BESTlogic expression: VO15=0