Table 6-11. protective functions with targets -18, Ee table 6-11) – Basler Electric BE1-700 User Manual

Page 150

Advertising
background image

Table 6-11. Protective Functions with Targets

Type

Name

Protective Function

Target

Default

C

51P

Phase Inverse Time Overcurrent

Enabled

C

51N

Neutral Inverse Time Overcurrent

Enabled

C

51Q

Negative-Sequence Inverse Time Overcurrent

Enabled

C

151P

Second Phase Time Overcurrent

Enabled

C

151N

Second Neutral Time Overcurrent

Enabled

C

50TP

Phase Instantaneous Overcurrent

Enabled

C

50TN

Neutral Instantaneous Overcurrent

Enabled

C

50TQ

Negative-Sequence Instantaneous Overcurrent

Enabled

C

150TP

Second Phase Instantaneous Overcurrent

Enabled

C

150TN

Second Neutral Instantaneous Overcurrent

Enabled

C

150TQ

Second Negative-Sequence Instantaneous Overcurrent

Enabled

V

81

Under/Overfrequency

Enabled

V

181

Second Under/Overfrequency

Enabled

V

281

Third Under/Overfrequency

Enabled

V

381

Fourth Under/Overfrequency

Enabled

V

481

Fifth Under/Overfrequency

Enabled

V

581

Sixth Under/Overfrequency

Enabled

V

59P

Phase Overvoltage

Enabled

V

159P

Second Phase Undervoltage

Enabled

V

59X

Auxiliary Overvoltage

Enabled

V

159X

Seconds Auxiliary Overvoltage

Enabled

V

47

Negative-Sequence Overvoltage

Enabled

V

27P

Phase Undervoltage

Enabled

V

127P

Second Phase Undervoltage

Enabled

V

27X

Auxiliary Undervoltage

Enabled

A

62

General Purpose Logic Timer

Disabled

A

162

Second General Purpose Logic Timer

Disabled

V

24

Volts per Hertz

Enabled

V

60FL

Fuse Loss Detection

Disabled

C

BF

Breaker Failure

Enabled

Target logging for a protective function can be disabled if the function is used in a supervisory or
monitoring capacity. The following paragraphs describe how the relay is programmed to define which
protective functions log targets.

Setting the Targets Function

Targets are enabled using the BESTCOMS screen shown in Figure 6-13. You can select which protective
elements trigger a target and what type of logic condition will reset the targets. To open the screen, select
Reporting and Alarms from the Screens pull-down menu. Then select the Fault Recording tab. Enable the
targets by checking the appropriate boxes.

Alternately, targets can be enabled using the SG-TARG ASCII command. Using the SG-TARG command,
you can select which protective elements trigger a target and what type of logic condition will reset the
targets.

6-18

BE1-700 Reporting and Alarm Functions

9376700990 Rev M