Automatic Setting Group Change

Purpose: To verify the operation of the automatic setting group change function.

Reference Commands: SL-GROUP, SG-SGCON, SP-GROUP, CS/CO-GROUP, SL-51, S<g>-51

Automatic Change

Step 1: Connect a current source to Terminals D1 and D2 (A-phase input).

Step 2: Prepare the automatic setting group change function for testing by transmitting the commands

in Table 13-94 to the relay.

Table 13-94. Automatic Setting Group Change Function Test Commands

Command

Purpose

A=

Gains write access.

SL-N=NONE

Zero out custom logic settings. Overwrite with LOGIC=NONE
settings.

Y

Confirm overwrite.

SL-N=ASG

Name custom logic for this test.

SL-GROUP=1,43,143,INI

Sets logic mode to discrete selection with virtual switch and
contact input control.

SL-51P=1,0

Enables 51P, disables blocking.

SG-SGCON=1S

Sets SGC on-time at 1 seconds.

SL-VO1=SG1

Closes OUT1 when SG1 is active.

SG-CTP=1

Sets the phase CT ratio at 1.

SG-TRIGGER=51PT,51PPU,0

Enable 51PT to log and trigger fault recording.

SL-43=3

Enables 43 Switch OFF/momentary ON mode.

SL-143=3

Enables 143 Switch OFF/momentary ON mode.

SN-43=MAN_SEL,GRP0,NORMAL

Assigns 43 Switch labels.

SN-143=MAN_SEL,GRP1,NORMAL Assigns 143 Switch labels.

SN-IN1=MAN_SEL,AUTO,MANUAL

Assigns IN1 Switch labels.

SP-GROUP1=1,75,1,70,51P

SG1 ts = 1 min @ 75%, tr = 1 min @ 70% of SG0 51P setting.

EXIT;Y

Exit and save settings.

Step 3: Select automatic setting group control by energizing Input IN1.

Step 4: Gain write access and transmit the appropriate setting commands in Table 13-95 to the relay.

Remember to save your setting changes with the EXIT;Y commands. An ohmmeter or
continuity tester may be used to monitor the output contacts (OUT1, OUT2, OUT3) status.

Table 13-95. 51P Element Pickup Settings

Sensing Type

Command

Comments

1 A

S0-51P=1.0,5.0,I2

pu = 1.0, td = 5, curve = I2

S0-51P=1.5,5.0,I2

pu = 1.5, td = 5, curve = I2

S0-51P=1.8,5.0,I2

pu = 1.8, td = 5, curve = I2

S0-51P=2.2,5.0,I2

pu = 2.2, td = 5, curve = I2

5 A

S0-51P=5.0,5.0,I2

pu = 5.0, td = 5, curve = I2

S0-51P=7.5,5.0,I2

pu = 7.5, td = 5, curve = I2

S0-51P=9.0,5.0,I2

pu = 9.0, td = 5, curve = I2

S0-51P=10.5,5.0,I2

pu = 10.5, td = 5, curve = I2

9376700990 Rev M

BE1-700 Testing and Maintenance

13-53