SG-IN Command
Purpose:

Read/Set Input recognition/debounce

Syntax:

SG-IN[#[={r(ms)},{db(ms)}]] where ms=1-255msec

Example:

SG-IN or SG-IN3 or SG-IN3=4,16

Reference:

Section 3, Input and Output Functions, Contact Sensing Inputs

SG-NOM Command
Purpose:

Read/Enter power system nominal Voltage & Current

Syntax:

SG-NOM[={Nom Volts},{Nom Amps}]

Example:

SG-NOM or SG-NOM=120,5 or SG-NOM=120,1

Reference:

Section 3, Input and Output Functions, Power System Inputs

SG-OSC Command
Purpose:

Read/Set the number of oscillograph fault records saved

Syntax:

SG-OSC[=6/8/10/12/15/16]

Example:

SG-OSC or SG-OSC=6

Reference:

Section 6, Reporting and Alarm Functions, Oscillographic Records

SG-PHROT Command
Purpose:

Read/Set Phase Rotation setting

Syntax:

SG-PHROT[={phase rotation}] ABC/ACB

Example:

SG-PHROT or SG-PHROT=ABC or SG_PHROT=ACB

Reference:

Section 3, Input and Output Functions, Power System Inputs

SG-SCREEN Command
Purpose:

Read/Set default screen(s)

Syntax:

SG-SCREEN[n][={default screen number}]

Example:

SG-SCREEN or SG-SCREEN1=2.2.1 or SG-SCREEN2=2.2.2

Reference:

Section 10, Human-Machine Interface, Front Panel Display

SG-SGCON Command
Purpose:

Read/Set SGC output on time

Syntax:

SG-SGCON[={time}] where time is in (s)ec

Example:

SG-SGCON or SG-SGCON=1S or SG-SGCON=5S

Reference:

Section 4, Protection and Control, Setting Groups

SG-TARG Command
Purpose:

Report/Enable Target List and Reset Target Logic

Syntax:

SG-TARG[={x/x/..x},{rst TARG logic}] where x=27,47,50,51,59,81,181 etc.

Example:

SG-TARG or SG-TARG=27/50/51N/59/81/281

Reference:

Section 6, Reporting and Alarm Functions, Fault Reporting

SG-TRIGGER Command
Purpose:

Read/Set Trigger logic

Syntax:

SG-TRIGGER[n][={TRIP trigger},{PU trigger},{LOGIC trigger}]

Example:

SG-TRIGGER or SG-TRIGGER=VO1,VO2,IN4

Reference:

Section 6, Reporting and Alarm Functions, Fault Reporting

SG-VTP Command (BE1-700V)
Purpose:

Read/Set VT ratio, connection, 27/59 sensing mode, 51/27R sensing mode

Syntax:

SG-VTP[={VT_ratio},{connection},{27/59mode},{51/27Rmode}]

Example:

SG-VTP or VTP=10,4W,PN,PN or VTP=1200:120,3W,PP,PP or VTP=1200/120,AB

Reference:

Section 3, Input and Output Functions, Power System Inputs