Table 13-40. 27p and 59p pickup test commands -28, Table 13-41. 27p and 59p pickup settings -28, N table – Basler Electric BE1-700 User Manual

Page 324

Advertising
background image

Table 13-40. 27P and 59P Pickup Test Commands

Command

Purpose

A=

Gains write access.

SL-N=NONE

Zero out custom logic settings. Overwrite with LOGIC=NONE
settings.

Y

Confirm overwrite.

SL-N=27_59

Sets 27_59 as custom logic name.

SG-VTP=1,4W,PN,PN

Set VT phase voltage parameters.

SA-MAJ=0

Disables Major Alarm.

SL-27P=1,0

Enables 27P, disables blocking.

SL-59P=1,0

Enables 59P, disables blocking.

SL-VO1=27PT+59PT

Enables OUT1 to close for 27P or 59P trip.

SG-TRIG=27PT+59PT,
27PPU+59PPU,0

Enables 27P and 59P to log and trigger fault record.

SG-TARG=27/127/59/159

Enables 27, 127, 59, and 159 targets.

EXIT;Y

Exit and save settings.

Step 2: Using Table 13-41 as a guide, transmit the first row of setting commands (highest 27P PU,

lowest 59P PU) to the relay.

Table 13-41. 27P and 59P Pickup Settings

Phase Pickup Settings

Purpose

Undervoltage

Overvoltage

S0-27P=96,50ms

S0-59P=132,50ms

Sets 27P PU at 96 V, 59P at 132 V, TD at min

S0-27P=84,50ms

S0-59P=144,50ms

Sets 27P PU at 84 V, 59P at 144 V, TD at min

S0-27P=72,50ms

S0-59P=156,50ms

Sets 27P PU at 72 V, 59P at 156 V, TD at min

Step 3: Prepare to monitor the 27P and 59P function operation. Operation can be verified by monitoring

OUT1.

Step 4: Connect and apply a 120 Vac, three-phase voltage source to Terminals C13 (A-phase), C14 (B-

phase), C15 (C-phase), and C16 (Neutral). Refer to Figure 12-4 for terminal locations.

Step 5: Slowly decrease the A-phase voltage until OUT1 closes. Pickup should occur within

±2 percent

or 1 volt of the 27P pickup setting. Slowly increase the A-phase voltage until OUT1 opens.
Dropout should occur between 102 and 103 percent of the actual pickup value. Verify the 27A
target and the HMI. Reset the target.

Step 6: Continue increasing the A-phase voltage until OUT1 closes. Pickup should occur within

±2

percent or 1 volt of the 59P pickup setting. Slowly reduce the A-phase voltage until OUT1
opens. Dropout should occur between 97 and 98 percent of the actual pickup value. Verify 59A
target on the HMI.

Step 7: Verify the pickup and dropout accuracy of the middle and upper pickup settings listed in Table

13-41.

Step 8: (Optional.) Repeat Steps 2 through 7 for the B-phase and C-phase voltage inputs.

Step 9: (Optional.) Repeat Steps 2 through 8 for Setting Group 1.

27/127 Phase Undervoltage Inhibit Pickup Test

Step 10: Using Table 13-42 as a guide, transmit the setting commands to the relay.

13-28

BE1-700 Testing and Maintenance

9376700990 Rev M