Figure 4-5. setting group selection screen -7 – Basler Electric BE1-700 User Manual

Page 63

Advertising
background image

Figure 4-5. Setting Group Selection Screen

Table 4-3. Operating Settings for Setting Group Control

Setting

Range

Purpose

Default

Switch Time

1 to 60

0 = Disabled

Time in minutes that determines when a setting
change occurs once the Switch Threshold setting is
exceeded.

0

Switch

Threshold

0 to 150

Percentage of the SG0 Monitor Setting that must be
exceeded for a setting group change to occur.

0

Return Time

1 to 60

0 = Disabled

Time in minutes that determines when a return to SG0
will occur once the monitored current has decreased
below the Return Threshold setting.

0

Return

Threshold

0 to 150

Percentage of the SG0 Monitor Setting that the
monitored current must decrease below in order for a
return to SG0.

0

Monitor Setting

51P, 51N, 151N,

51Q (BE1-700C

only); 60FL (BE1-

700V only); 791,
792, 793, or 794

Determines when automatic setting group changes
occur. Time overcurrent elements 51P, 51N, 151N, or
51Q can be selected so that setting group changes
are based on load current. Recloser Shots 791, 792,
793, or 794 can be used to switch setting groups
when the appropriate shot is reached in a reclosing
sequence. Fuse Loss (60FL) can also be used to
switch setting groups. If 60FL or one of the recloser
shots is entered as the Monitor Setting, the Switch
Time, Switch Threshold, Return Time, and Return
Threshold
parameters are not required.

51P

Setting Group

Change (SGC)

Alarm Timer

1 to 10

0 = Disabled

Measured in seconds, the SGC alarm timer sets the
amount of time the alarm is on.

5

9376700990 Rev M

BE1-700 Protection and Control

4-7

Advertising
This manual is related to the following products: