Figure 4-26. BESTlogic Function Element Screen, 59X

Table 4-18 summarizes the BESTlogic settings for Auxiliary Undervoltage/Overvoltage Protection.

Table 4-18. BESTlogic Settings for Auxiliary Undervoltage/Overvoltage Protection

Function

Range/Purpose

Default

Mode

0 = Disabled
1 = Fundamental Vx Input

2 = 3Vo Phase Inputs

3 = 3

rd

Harmonic, Vx Input

0

BLK

Logic expression that disables function when
TRUE. A setting of 0 disables blocking.

0

∗ To use Mode 2, the VTP connection must be 4-wire. Optional Auxiliary Input must be present to use
Mode 1 or Mode 3.

Operating Settings for Auxiliary Undervoltage/Overvoltage Protection

Operating settings for the 27X and 59X functions consist of pickup and time delay values. The pickup
value determines the level of voltage required for the element to start timing toward a trip. Unit of measure
is secondary volts (PP or PN) and depends on the VTX setting see Table 4-19. For more information,
refer to Section 3, Input and Output Functions, Power System Inputs, Voltage Measurement. The time
delay value determines the length of time between pickup and trip. Time delays can be set in
milliseconds, seconds, or cycles. The default is milliseconds if no unit of measure is specified.

Table 4-19. VTX Connection Settings

VTX Connection

Mode

Unit

AB, BC, CA

1 or 3

VPP

AN, BN, CN

1 or 3

VPN

GR

1 or 3

VPN

Don’t care

2

VPN

9376700990 Rev M

BE1-700 Protection and Control

4-31