Table 13-11. 50t and 150t time delay settings -16 – Basler Electric BE1-700 User Manual

Page 312

Advertising
background image

In addition, the pickup settings made in Step 3 (Table 13-7) must be changed to specify the
setting group being tested. To test settings in Group 1, replace the 0 in the S0-x50 commands
with a 1 (S1-x50).

50TP/150TP and TN (Calculated 3Io) Time Delay Verification

Step 1: Connect a current source to Terminals D1 and D2 (A-phase). Refer to Figure 12-3 for terminal

locations.

Step 2: Prepare the 50T/150T elements for testing by transmitting the commands in Table 13-10 to the

relay.

Table 13-10. 50TP and 50TN Time Delay Test Commands

Command

Purpose

A=

Gains write access.

SL-N=NONE

Zero out custom logic settings. Overwrite with LOGIC=NONE settings.

Y

Confirm overwrite.

SL-N=TD50

Sets TD50 as custom logic name.

SL-50TP=1,0; SL-50TN=1,0

Enables 50TP and 50TN (3Io), and disables blocking.

SL-VO1=50TPT

Enables OUT1 to close for 50TP trip.

SL-VO2=50TNT

Enables OUT2 to close for 50TN trip.

SG-CT=1

Sets P, N CT ratio at 1:1

SG-TRIG=50TPT+50TNT,
50TPPU+50TNPU,0

Enable 50TPT or 50TNT to log and trigger fault recording.

EXIT;Y

Exit and save settings.

Step 3: Using Table 13-11, transmit the first column of setting commands.

Table 13-11. 50T and 150T Time Delay Settings

Pickup and Time Delay Settings

Purpose

2 Second TD

5 Second TD

10 Second TD

S0-50TP=0.5,2S

S0-50TP=0.5,5S

S0-50TP=0.5,10S

Sets 50TP TD.

S0-50TN=0.5,2S

S0-50TN=0.5,5S

S0-50TN=0.5,10S

Sets 50TN TD.

Step 4: Step the applied A-phase current to .55 amps (for 1 amp CT circuit divide by 5). Measure the

time delay and verify the accuracy of the 50TP time delay setting, OUT1, and 50TN, OUT2.
Timing accuracy is

±5 percent or ±3 cycles of the time delay setting.

Step 5: Repeat Steps 2 and 3 for the middle and higher time delay settings in Table 13-11.

Step 6: (Optional.) Repeat Steps 3 through 5 for phase B (Terminals D3 and D4), phase C (Terminals

D5 and D6).

Step 7: (Optional.) Repeat Steps 1 through 6 for the 150T elements. Overwrite the 50T commands

entered in Step 2 with the commands of Table 13-12.

Table 13-12. 150TP and 150TN Time Delay Test Commands

Command

Purpose

A=

Gains write access.

SL-150TP=1,0; SL-150TN=1,0

Enables 150TP and 150TN, disables blocking.

SL-VO1=150TPT

Enables OUT1 to close for 150TP trip.

SL-VO2=150TNT

Enables OUT2 to close for 150TN trip.

SG-TRIGGER=150TPT+150TNT,

Enable 150TPT or 150TNT to log and trigger fault recording.

13-16

BE1-700 Testing and Maintenance

9376700990 Rev M

Advertising
This manual is related to the following products: