Frequency Range

Options 1, 2, and 4 only:

40 to 70 Hz

Burden

Options 1, 2, 3, 4, 5:

8 W continuous, 11 W maximum with all outputs
energized

Output Contacts

Make and Carry for Tripping Duty:

30 A for 0.2 seconds per IEEE C37.90;
7 A continuous

Break Resistive or Inductive:

0.3 A at 125 or 250 Vdc (L/R = 0.04 maximum)

Contact-Sensing Inputs

Contact-sensing turn-on voltages and burdens are listed in Table 1-2. Burden values assume nominal
value of input voltage applied.

Table 1-2. Contact-Sensing Turn-On Voltages and Burdens

Style Option

Nominal Input Voltage

Contact-Sensing Turn-On Voltage

*

Burden

xxx1xxx

48 Vdc

26 to 38 Vdc

23 k

xxx2xxx

125 Vac/dc

69 to 100 Vdc

56 to 97 Vac

53 k

xxx3xxx

24 Vdc

Approx. 5 Vdc

6 k

xxx4xxx

250 Vac/dc

138 to 200 Vdc
112 to 194 Vac

123 k

xxx5xxx

125 Vac/dc †

69 to 100 Vdc

56 to 97 Vac

53 k

* AC voltage ranges are calculated using the default recognition time (4 ms) and debounce time (16 ms).
† Extended holdup option. See Style Chart in Figure 1-1.

Recognition Time

Programmable ................................................................ 4 to 255 ms

IRIG

Supports IRIG Standard 200-98, Format B002
Input Signal:

Demodulated (dc level-shifted digital signal)

Logic-High Voltage:

3.5 Vdc, minimum

Logic-Low Voltage:

0.5 Vdc, maximum

Input Voltage Range:

±20 Vdc, maximum

Resistance:

Nonlinear, approximately 4 k

Ω at 3.5 Vdc,

approximately 3 k

Ω at 20 Vdc

NOTE

All timing specifications are for the worst-case response. This includes output
contact operate times and standard BESTlogic operation timing but excludes
input debounce timing and non-standard logic configurations. If a non-standard
logic scheme involves feedback, then one or more BESTlogic update rate delays
must be included to calculate the worst-case delay. An example of feedback is
Virtual Outputs driving Function Block Inputs. For more information, see Section
7, BESTlogic Programmable Logic.