Manual Change - Mode 1

Manual Change Mode 1 test procedures are a continuation of the automatic test procedures. Do not
change the logic or settings except for those in Step 1 and subsequent.

Step 1: De-energize IN1 and verify that VO1 goes TRUE and closes OUT1 when SG1 becomes the

active setting group.

Step 2: Transmit the select and operate commands in Table 13-99 to the relay.

Table 13-99. Manual Setting Group Control Selection

Command

Purpose

A=

Gains write access.

CS-143=0

Selects 143 for FALSE operation.

CO-143=0

Executes 143 FALSE operation.

CS-43=1

Selects 43 for TRUE operation.

CO-43=1

Executes 43 TRUE operation.

CS-43=0

Selects 43 for FALSE operation.

CO-43=0

Executes 43 FALSE operation.

EXIT

Exit select and operate mode.

Step 3: Use the RS-LGC command to retrieve logic variable data from the SER. Verify that the setting

group change actions were logged.

Manual Change - Mode 2

Manual Change Mode 2 test procedures are a continuation of the Mode 1 test procedures. Do not change
the logic or settings except for those in Step 1 and subsequent.

Step 1: Transmit the commands in Table 13-100 to the relay. These commands set up the relay for

binary setting group control selection.

Table 13-100. Binary Group Control Selection Setup

Command

Purpose

A=

Gains write access.

SL-GROUP=2,43,0,143

Configures the setting group control function as binary coded selection.
D0 logic = 43, D1 logic = 0, Auto logic = 143

SL-43=2

Sets 43 to On/Off mode.

EXIT;Y

Exit and save settings.

Step 2: Transmit the select and operate commands in Table 13-101 to the relay. For more information

on setting group selection, see Section 4, Protection and Control, Setting Groups.

Table 13-101. Binary Group control Select and Operate Commands

Command

Purpose

A=

Gains write access.

CS-43=0

Selects 43 for FALSE operation.

CO-43=0

Executes 43 FALSE operation.

EXIT

Exit select and operate mode.

Step 3: Verify that VO1 goes FALSE and opens OUT1 when SG0 becomes the active setting group.

9376700990 Rev M

BE1-700 Testing and Maintenance

13-55