Table 13-59. x81 Pickup Test Commands

Command

Purpose

A=

Gains write access.

SL-N=NONE

Zero out custom logic settings. Overwrite with
LOGIC=NONE settings.

Y

Confirm overwrite.

SL-N=FREQTEST

Sets FREQTEST as custom logic name.

SL-81=1,0

Enables 81, disables blocking.

SL-181=1,0

Enables 181, disables blocking.

SL-281=1,0

Enables 281, disables blocking.

SL-381=1,0

Enables 381, disables blocking.

SL-481=1,0

Enables 481, disables blocking.

SL-581=1,0

Enables 581, disables blocking.

SL-VO1=81T+581T

Enables OUT1 to close for 81 or 581 trip.

SL-VO2=181T

Enables OUT2 to close for 181 trip.

SL-VO3=281T

Enables OUT3 to close for 281 trip.

SL-VO4=381T

Enables OUT4 to close for 381 trip.

SL-VO5=481T

Enables OUT5 to close for 481 trip.

SG-TARG=81/181/281/381/481/581

Enables 81, 181, 281, 381, 481, and 581 targets.

SG-
TRIG=81T+181T+281T+381T+481T+581T

Sets fault trigger on any x81.

EXIT;Y

Exit and save settings.

Step 2: Transmit the commands in Table 13-60 to the relay. These commands set the voltage inhibit

value, pickup value, and operating mode (Underfrequency or Overfrequency) for each of the
x81 functions.

Table 13-60. x81 Pickup and Mode Settings

Pickup and Mode Settings

Purpose

S0-81INH=40

Set PU = 40V

S0-81=42,0,U

Sets 81 PU at 42 Hz, Underfrequency.

S0-181=46,0,U

Sets 181 PU at 46 Hz, Underfrequency.

S0-281=48,0,U

Sets 281 PU at 48 Hz, Underfrequency.

S0-381=65,0,O

Sets 381 PU at 65 Hz, Overfrequency.

S0-481=67,0,O

Sets 481 PU at 67 Hz, Overfrequency.

S0-581=69,0,O

Sets 581 PU at 69 Hz, Overfrequency.

Step 3: Prepare to monitor x81 function operation. Operation can be verified by monitoring the

programmed output contacts or HMI Screen 1.5.2.

Step 4: Connect and apply a 120 Vac, 60-hertz voltage source to Terminals C13 (A-phase) and C16

(neutral).

Step 5: Slowly decrease the frequency of the applied voltage until OUT3 (281) closes. Pickup should

occur within

±0.01 hertz of the pickup setting. Slowly increase the frequency until OUT3 opens.

Dropout should occur at 0.02 hertz above or below the pickup setting.

Step 6: Lower the frequency until OUT3 again closes. Lower the source voltage until OUT3 drops out

(under voltage inhibit level), raise the voltage until OUT3 picks up. Pickup should occur

±2% of

the voltage inhibit setting and drop out at 95% of pickup.