Figure 14-28. Reporting and Alarms Screen, Breaker Monitoring Tab

Alarms

BE1-700 relays have 33 programmable alarm points. See Figure 14-29. These points are for the
monitored power system, associated equipment and non-core circuits, and functions in the relay. Each of
these alarm points can be programmed to assert the Major, Minor, or Logic Alarms when an alarm point is
activated. To program an alarm point, find the point in the Alarm Priority list and then click on the
appropriate field under the Major, Minor, or Logic Alarm.

Logic settings for the Alarm Reset Logic can be made by clicking on the BESTlogic logic button and then
clicking on the reset input. Other logic blocks shown under BESTlogic on the Alarms tab are shown for
reference only. There is no interaction available.

Figure 14-29. Reporting and Alarms Screen, Alarms Tab