Step 2: Using Table 13-49 as a guide, transmit the first row of setting commands (highest 27X PU,

lowest 59XPU/159XPU) to the relay.

Table 13-49. 27X and 59X/159X Pickup Settings

Pickup and Time Delay Settings

Purpose

Undervoltage

Overvoltage

S0-27X=70,50ms,0

S0-59X/159X=90,50ms

Sets 27X PU at 70 V, 59X/159X at 90 V, TD
at min, UV Inhibit disabled.

S0-27X=60,50ms,0

S0-59X/159X=100,50ms

Sets 27X PU at 60 V, 59X/159X at 100 V,
TD at min, UV Inhibit disabled.

S0-27X=50,50ms,0

S0-59X159X=110,50ms

Sets 27X PU at 50 V, 59X/159X at 110 V,
TD at min, UV Inhibit disabled.

Step 3: Prepare to monitor the 27X and 59X/159X function operation. Operation can be verified by

monitoring OUT1.

Step 4: Connect and apply a single-phase, 80 Vac voltage source to VX Input, Terminals C17 (polarity)

and C18 (non-polarity). Refer to Figure 12-4 for terminal locations.

Step 5: Slowly decrease the voltage until OUT1 closes. Pickup should occur within

±2 percent or 1 volt

of the pickup setting. Slowly increase the voltage until OUT1 opens. Dropout should occur
between 102% and 103% of the actual pickup value. Verify the 27 bus target on the HMI and
reset.

Step 6: Continue to increase the voltage until OUT1 closes. Pickup should occur within

±2 percent or 1

volt of the pickup setting. Slowly reduce the voltage until OUT1 opens. Dropout should occur
between 97% and 98% of the actual pickup value. Verify the 59 Bus target on the HMI.

Step 7: Verify the pickup and dropout accuracy of the middle and upper pickup settings listed in Table

13-49.

Step 8: (Optional.) Repeat Steps 2 through 7 for Setting Group 1.

27X Auxiliary Undervoltage Inhibit Pickup Test (Fundamental VX Test)

Step 1: Using Table 13-50 as a guide, transmit the first row of setting commands to the relay.

Table 13-50. 27X and 59X/159X Pickup Settings

Pickup and Time Delay Settings

Purpose

Undervoltage

Overvoltage

S0-27X=70,50ms,50

S0-59X/159X=90,50ms

Sets 27X PU at 70 V, 59X/159X at 90 V, TD
at min, UV Inhibit at 50V.

S0-27X=60,50ms,50

S0-59X/159X=100,50ms

Sets 27X PU at 60 V, 59X/159X at 100 V,
TD at min, UV Inhibit at 50V.

S0-27X=50,50ms,50

S0-59X159X=110,50ms

Sets 27X PU at 50 V, 59X/159X at 110 V,
TD at min, UV Inhibit at 50V.

Step 2: Prepare to monitor the 27X and 59X/159X function operation. Operation can be verified by

monitoring OUT1.

Step 3: Connect and apply a single-phase, 80 Vac voltage source to VX Input, Terminals C17 (polarity)

and C18 (non-polarity). Refer to Figure 12-4 for terminal locations.

Step 4: Slowly decrease the voltage until OUT1 closes. Pickup should occur within

±2 percent or 1 volt

of the pickup setting. Continue to decrease the voltage until OUT1 opens. UV inhibit pickup
should occur within

±3 percent of 50V. Increase the voltage until OUT1 closes. UV inhibit

dropout should occur at

±5 percent of inhibit pickup.

Step 5: (Optional.) Repeat Steps 1 through 4 for Setting Group 1.

13-32

BE1-700 Testing and Maintenance