Basler Electric BE1-700 User Manual

Page 78

Advertising
background image

Figure 4-16. BESTlogic Function Element Screen, 24

Table 4-13 lists the BESTlogic settings for Overexcitation Protection.

Table 4-13. BESTlogic Settings for Volts per Hertz Overexcitation

Function

Range/Purpose

Default

Mode

0 = Disable
1 = Enable

0

BLK

Logic expression that disables the function when TRUE.

0

Operating Settings for Overexcitation Protection

Operating settings for the 24 function consist of a pickup setting, a trip time dial, and a reset time dial. A
pickup of 0 disables the element. The unit of measure is secondary VPP/Hz or VPN/Hz and depends on
the SG-VTP setting. For more information, refer to Section 3, Input and Output Functions, Power System
Inputs
. Operating settings are made using BESTCOMS. Figure 4-17 illustrates the BESTCOMS screen
used to select operational settings for the Overexcitation element. To open the screen, select Voltage
Protection
from the Screens pull-down menu and select the 24 Tab. Alternately, settings can be made
using the S<g>-24 and S<g>-24D commands or at the front panel HMI using Screen 5.x.1.1 where x
equals 1 or 2, for Setting Group 0 or 1.

4-22

BE1-700 Protection and Control

9376700990 Rev M

Advertising