27p phase undervoltage protection (be1-700v), 27x auxiliary undervoltage protection (be1-700v), 27p phase undervoltage protection (be1-700v) -8 – Basler Electric BE1-700 User Manual

Page 20

Advertising
background image

27P Phase Undervoltage Protection (BE1-700V)

Pickup

Setting Range:

10 to 300 V

Accuracy:

±2% of setting or ±1 V, whichever is greater

Dropout/Pickup Ratio:

102%

Time Delay

Setting Range:

0.05 to 600 s

Accuracy:

±0.5% or ±2.5 cycles, whichever is greater

27X Auxiliary Undervoltage Protection (BE1-700V)

Pickup

Setting Range:

1 to 150 V

Accuracy:

±2% of setting or ±1 V, whichever is greater

Dropout/Pickup Ratio:

102%

Time Delay

Setting Range:

0.05 to 600 s

Accuracy:

±0.5% or ±2.5 cycles, whichever is greater

47 Negative-Sequence Overvoltage Protection (BE1-700)

Pickup

Setting Range:

1.0 to 300 V

L-N

Accuracy:

±2% of setting or ±1 V, whichever is greater

Dropout/Pickup Ratio:

98%

Time Delay

Setting Range:

0.050 to 600 s

Accuracy:

±0.5% or ±2.5 cycles, whichever is greater

50T Instantaneous Overcurrent Protection (BE1-700C)

Pickup

Setting Range

5 Ampere CT:

0.5 to 150 A

1 Ampere CT:

0.1 to 30 A

Accuracy (50TP, 50TN)

5 Ampere CT:

±2% or ±50 mA, whichever is greater

1 Ampere CT:

±2% or ±10 mA, whichever is greater

Accuracy (50TQ)

5 Ampere CT:

±3% or ±75 mA, whichever is greater

1 Ampere CT:

±3% or ±15 mA, whichever is greater

Dropout/Pickup Ratio:

95%

Time Delay

Setting Range:

0 to 60 s

Accuracy

50TP, 50TN:

±0.5% or ±½ cycle, whichever is greater, plus trip
time for instantaneous response (0.0 setting)

*

50TQ:

±0.5% or ±1 cycle, whichever is greater, plus trip
time for instantaneous response (0.0 setting)

*

1-8

BE1-700 General Information

9376700990 Rev M

Advertising