Table 13-34. v/hz trip time settings -26, Table 13-35. v/hz trip times -26, Table 13-36. v/hz reset time pickup settings -26 – Basler Electric BE1-700 User Manual

Page 322: Ng table 13-34

Advertising
background image

Table 13-34. V/Hz Trip Time Settings

Settings

Purpose

S0-24=2.1,0.5,0.0,2.0

Sets integrating 24 PU at 1.05% of nominal (2.10 V/Hz), Trip Time
Dial = 0.5, Reset Time Dial = 0, Time Curve Exponent = 2.

Step 2: Connect a 120 Vac, three-phase, 50 or 60-hertz voltage source (depending on user's nominal

frequency) to Terminals C13 (A-phase), C14 (B-phase), C15 (C-phase), and C16 (neutral).
Refer to Figure 12-4 for terminal locations.

Step 3: All integrating timing tests are based on % of nominal Volts/Hertz (1 PU value). Refer to

Appendix D of the BE1-700 instruction manual for time curves. Apply A-phase voltage at
nominal frequency and a value of voltage that equals the V/Hz % of nominal shown in Table
13-35
for Time Dial 0.5. Measure the time between the application of voltage and the closure of
OUT1. Verify that the relay operates within

±5% of the values shown in Table 13-35.

Table 13-35. V/Hz Trip Times

Percent of Nominal

V/Hz

Time Dial 0.5

Time Dial 1.0

Time Dial 2.0

110%

50 seconds

100 seconds

200 seconds

120%

12.5 seconds

25 seconds

50 seconds

140%

3.1 seconds

6.3 seconds

12.5 seconds

Step 4: Repeat the test for Time Dial 1.0 and 2.0.

Step 5: (Optional.) Repeat Steps 2 through 4 for the B-phase and C-phase voltage inputs.

Step 6: (Optional.) Repeat Steps 2 through 5 for Setting Group 1.

Overexcitation, Volts/Hertz Linear Reset Time Verification

The following reset time test is an approximation. For a more precise test, use a computer driven test set
and the integration time equations found in Section 4, Protection and Control, Voltage Protection, 24
Element
, or Appendix D, Overexcitation (24) Inverse Time Curves.

Step 1: Using Table 13-36 as a guide, transmit the setting commands to the relay.

Table 13-36. V/Hz Reset Time Pickup Settings

Setting

Purpose

S0-24=2.1,0.5,0.2,2.0

Sets 24 PU at 1.05% of nominal (2.10 V/Hz), Trip Time Dial = 0.5,
Reset Time Dial = 0.2, Time Curve Exponent = 2.

Step 2: Connect a 120 Vac, three-phase, 50 or 60-hertz voltage source (depending on user's nominal

frequency) to Terminals C13 (A-phase), C14 (B-phase), C15 (C-phase), and C16 (neutral).
Refer to Figure 12-4 for terminal locations.

Step 3: Apply A-phase voltage at nominal frequency and a value of voltage that equals the V/Hz % of

nominal shown in Table 13-37. Measure the time between the application of voltage and the
closure of OUT1 (12.5 seconds). Remove the test voltage and reapply after 5 seconds has
elapsed.

With a Reset Time Dial setting of 0.2, the total time to reset, after trip is removed, will be
approximately 10 seconds. (See Section 4, Protection and Control, Voltage Protection, for more
details.) Reapplying the test voltage after 5 seconds will yield a trip time of approximately ½ its
original value or 6.25 seconds for Trip Time Dial 0.5 verifying that the reset time delay is
working.

13-26

BE1-700 Testing and Maintenance

9376700990 Rev M

Advertising
This manual is related to the following products: