Figure 8-2. 700C-5051-A-BE (Basic OC) One-Line Drawing

Table 8-1. 700C-5051-A-BE (Basic OC) Contact Sensing Input Logic

Input

Purpose

Label

State Labels

Energized

De-Energized

IN1

Optional input used for breaker status indication in Sequence
of Events Reporting. TRUE when breaker is open. Typically,
IN1 is connected to the 52b contact of the breaker.

BREAKER

CLOSED

OPEN

IN2

Not used

INPUT_2

CLOSED

OPEN

IN3

Not used

INPUT_3

CLOSED

OPEN

IN4

Not used

INPUT_4

CLOSED

OPEN

Table 8-2. 700C-5051-A-BE (Basic OC) Function Block Logic

Function

Purpose

BESTlogic

Expression

Mode Setting

50TP

Used for instantaneous phase overcurrent protection

0

1 (enabled)

50TN

Used for instantaneous neutral overcurrent protection.

0

1 (3-phase

Residual)

52

51P

51N

51Q

50TP

50TN

50TQ

OUT2

OUT4

OUT3

OUT5

OUT1

TRIP

BE1-700C

D2849-50

10-05-04

9376700990 Rev M