Basler Electric BE1-700 User Manual

Page 196

Advertising
background image

Function

Purpose

BESTlogic

Expression

Mode Setting

GROUP

Input 0 Logic: No manual selection logic is used

0

1

(discrete input

selection)

Input 1 Logic: No manual selection logic is used

0

Auto/Manual Logic: Set to 1 (/0) to enable automatic
selection. No manual selection is used.

/0

Table 8-8. 700C-OC79-A-BE (OC with 79) Virtual Switch Logic

Switch

Purpose

Mode

Label

State Labels

TRUE

FALSE

43

Not used

0 (disabled)

SWITCH_43

Closed

Open

143

Not used

0 (disabled)

SWITCH_143

Closed

Open

101

Not used

0 (disabled)

N/A

N/A

N/A

Table 8-9. 700C-OC79-A-BE (OC with 79) Virtual Output Logic

Output

Purpose

Output Description

Label

State Labels

TRUE

FALSE

VOA

(OUTA)

Alarm Output Contact

Alarm contact closes automatically
when relay trouble alarm occurs.

ALARM

Active

Normal

BESTlogic expression: VOA=0

VO1

(OUT1)

Breaker Trip Contact

Contact closes when protective trip
expression is TRUE.

BKR_TRIP

Trip

Normal

BESTlogic expression: VO1=VO11

VO2

(OUT2)

Breaker Close Contact

Close breaker when recloser close
output is TRUE.

BKR_CLOSE

Closed

Normal

BESTlogic expression: VO2=79C

VO3

(OUT3)

Not used

VO3

True

False

BESTlogic expression: VO3=0

VO4

(OUT4)

Minor Alarm

Closes contact when Minor Alarm
expression is TRUE

ALMMIN

Active

Normal

BESTlogic expression: VO4=ALMMIN

8-14

BE1-700 Application

9376700990 Rev M