background image

RF Command
Purpose:

Read/Reset Fault Report Data

Syntax:

RF[-n/NEW][=0/TRIG] where n=record # or NEW = new records

Example:

RF (displays a directory of all fault reports in memory)

RF-23 (view summary report for fault record 23)

RF-NEW (view summary report for newest fault record since RF=0 reset)

RF=TRIG (Manually Trigger a fault record)

RF=0 (reset NEW fault counter)

Reference:

Section 6, Reporting and Alarm Functions, Fault Reporting

RG Command
Purpose:

Report General information

Syntax:

RG

Example:

RG

Reference:

Section 6, Reporting and Alarm Functions, Clock

Section 6, Reporting and Alarm Functions, Fault Reporting

RG-DATE Command
Purpose:

Report/Set Date

Syntax:

RG-DATE[={M/D/Y}] or RG-DATE[={D-M-Y}]

Example:

RG-DATE=12/31/96 or RG-DATE=31-12-96 (Format set by SG-CLK Command)

Reference:

Section 6, Reporting and Alarm Functions, Clock

RG-STAT Command
Purpose:

Report relay status

Syntax:

RG-STAT

Example:

RG-STAT

Reference:

Section 6, Reporting and Alarm Functions, General Status Reporting

RG-TARG Command
Purpose:

Report/Reset Target status

Syntax:

RG-TARG

Example:

RG-TARG or RG-TARG=0

Reference:

Section 6, Reporting and Alarm Functions, Fault Reporting

RG-TIME Command
Purpose:

Report/Set Time

Syntax:

RG-TIME[=hr:mn:sc] or RG-TIME[=hr:mn{f}sc]]

Example:

RG-TIME=13:25:00 or RG-TIME=1:25P00 (Format(f) set by SG-CLK Command)

Reference:

Section 6, Reporting and Alarm Functions, Clock

RG-VER Command
Purpose:

Read Model #, Style #, Program Version, Serial #

Syntax:

RG-VER

Example:

RG-VER

Reference:

Section 6, Reporting and Alarm Functions, Hardware and Software Version Reporting

RO Command
Purpose:

Read Oscillographic COMTRADE .DAT/.CFG/.HDR Fault Report

Syntax:

RO-nA/B[#].CFG/DAT/HDR where n=report number,A=ASCII/B=BINARY,#=OSC 1/2

Example:

RO-3A1.CFG or RO-3A1.DAT or RO-5B2.CFG or RO-5B2.DAT or RO-5A.HDR

Reference:

Section 6, Reporting and Alarm Functions, Fault Reporting