Setting programmable curves -16, Equation 4-1, Equation 4-2 – Basler Electric BE1-700 User Manual

Page 72: N table 4-10

Advertising
background image

Equation 4-1. Time OC Characteristics for Trip

K

BD

C

M

AD

T

N

T

+

+

=

Equation 4-2. Time OC Characteristics for Reset

1

2

=

M

RD

T

R

Table 4-10. Definitions for Equations 4-1 and 4-2

Parameter

Description

Explanation

T

T

Time to trip

Time that the 51 function will take to time out and trip.

D

Time dial setting

Time dial setting for the 51 function.

M

Multiple of pickup

Measured current in multiples of pickup. The timing algorithm has a
dynamic range of 0 to 40 times pickup.

A

Coefficient specific
to selected curve

Affects the effective range of the time dial.

B

Coefficient specific
to selected curve

Affects a constant term in the timing equation. Has greatest effect
on curve shape at high multiples of tap.

C

Coefficient specific
to selected curve

Affects the multiple of PU where the curve would approach infinity if
allowed to continue below pickup. Has greatest effect on curve
shape near pickup.

N

Exponent specific
to selected curve

Affects how inverse the characteristics are. Has greatest effect on
curve shape at low to medium multiples of tap.

K

Constant

Characteristic minimum delay term.

T

R

Time to reset

Relevant if 51 function is set for integrating reset.

R

Coefficient specific
to selected curve

Affects the speed of reset when integrating reset is selected.

Setting Programmable Curves

Curve coefficients are entered using BESTCOMS. Alternately, curve coefficients can be entered using the
SP-CURVE ASCII (Settings Protection-programmable curve) command. Table 4-11 lists the
programmable curve settings.

Table 4-11. Programmable Time Current Characteristic Curve Coefficients

Setting

Range

Increment

Default

A Coefficient

0 to 600

0.0001

0.2663

B Coefficient

0 to 25

0.0001

0.0339

C Coefficient

0.0 to 1.0

0.0001

1.0000

N Coefficient

0.5 to 2.5

0.0001

1.2969

R Coefficient

0 to 30

0.0001

0.5000

Curve coefficients are entered by selecting the Curve Coefficients button on the 51 tab in the Time
Overcurrent
screen. (Refer to Figure 4-11.) The Curve Coefficients screen will appear (see Figure 4-12).
Enter the calculated values for each constant and select Done.

Programmable curve coefficients can be entered regardless of the curve chosen for the protection
element. However, the programmable curve will not be enabled until P is selected as the curve for the
protective element.

4-16

BE1-700 Protection and Control

9376700990 Rev M