Table 13-42. 27p uv inhibit pickup settings -29, Ng table 13-42 – Basler Electric BE1-700 User Manual

Page 325

Advertising
background image

Table 13-42. 27P UV Inhibit Pickup Settings

Phase Inhibit Pickup Settings

Purpose

Undervoltage

S0-27P=96,50ms,50

Sets 27P PU at 96 V, Time Dial at minimum, UV Inhibit at 50 V.

Step 11: Using the same test connections as Step 4 above, slowly decrease the A-phase voltage until

OUT1 closes. Pickup should occur within

±2 percent or 1 volt of the 27P pickup setting.

Step 12: Continue to decrease the voltage until OUT1 opens. UV inhibit pickup should occur within

±3

percent of 50 V. Increase the voltage until OUT1 closes. UV inhibit dropout should occur at

±5

percent of inhibit pickup.

Step 13: (Optional.) Repeat Steps 1 and 2 for 127P.

Step 14: (Optional.) Repeat Steps 1 through 3 for Setting Group 1.

Phase Undervoltage and Overvoltage Timing Verification

Step 1: Using Table 13-43 as a guide, transmit the first row of setting commands to the relay.

Table 13-43. 27P and 59P Pickup and Time Delay Settings

Phase Pickup and Time Delay Settings

Purpose

Undervoltage

Overvoltage

S0-27P=72,2s

S0-59P=156,2s

Sets 27P PU at 72 V, 59P at 156 V, TD at 2 sec

S0-27P=,5s

S0-59P=,5s

Sets 27P PU at 72 V, 59P at 156 V, TD at 5 sec

S0-27P=,10s

S0-59P=,10s

Sets 27P PU at 72 V, 59P at 156 V, TD at 10 sec

Step 2: Prepare to monitor the 27P and 59P timings. Timing accuracy is verified by measuring the

elapsed time between a sensing voltage change and OUT1 closing.

Step 3: Connect and apply a 120 Vac, three-phase voltage source to Terminals C13 (A-phase), C14 (B-

phase), C15 (C-phase), and C16 (neutral). Refer to Figure 12-4 for terminal locations.

Step 4: Step the A-phase voltage down to 68 volts. Measure the time delay and verify the accuracy of

the 27P time delay setting. Timing accuracy is

±5 percent or ±3 cycles of the time delay setting.

Step 5: Step the A-phase voltage up to 165 volts. Measure the time delay and verify the accuracy of the

59P time delay setting. Timing accuracy is

±5 percent or ±3 cycles of the time delay setting.

Step 6: Repeat Steps 5 and 6 for the middle and upper time delay settings of Table 13-43.

Step 7: (Optional.) Repeat Steps 2 through 6 for the B-phase and C-phase voltage inputs.

Step 8: (Optional.) Repeat Steps 2 through 7 for Setting Group 1.

Auxiliary Undervoltage and Overvoltage Pickup Verification (3V0 VT Input)

Step 1: Prepare the 27X and 59X/159X pickup function for testing by transmitting the commands in

Table 13-44 to the relay. Reset targets.

Table 13-44. 27X and 59X/159X Pickup Test Commands

Command

Purpose

A=

Gains write access.

SL-N=NONE

Zero out custom logic settings. Overwrite with LOGIC=NONE
settings.

Y

Confirm overwrite.

SL-N=27X/59/159X

Sets 27X/59/159X as custom logic name.

SL-27X=2,0

Enables 27X (3E0), disables blocking.

SL-59X=2,0

Enables 59X, disables blocking.

9376700990 Rev M

BE1-700 Testing and Maintenance