Basler Electric BE1-700 User Manual

Page 252

Advertising
background image

SG Command Example:
Example 1.

Obtain a report of all general settings.

>SG

SG-FREQ=60

SG-EMAIL1=0; SG-EMAIL2=0; SG-EMAIL3=0; SG-EMAIL4=0

SG-EMAIL5=0; SG-EMAIL6=0; SG-EMAIL7=0

SG-FREQ=60

SG-PHROT=ABC

SG-CTP=1

SG-CTG=1

SG-NOM= 0.0,5.00

SG-IN1= 4, 16; SG-IN2= 4, 16; SG-IN3= 4, 16; SG-IN4= 4, 16

SG-HOLDA=0; SG-HOLD1=1; SG-HOLD2=1; SG-HOLD3=0

SG-HOLD4=0; SG-HOLD5=1

SG-SGCON= 5

SG-DIP=15; SG-DIN= 1; SG-DIQ= 1

SG-LOG=15

SG-TARG=BF/50TP/150TP/50TN/150TN/50TQ/150TQ/51P/151P/62/162/51N/
151N/51Q,0

SG-TRIGGER=VO11,VO12,0

SG-OSC=16

SG-ID=BE1-700,SUBSTATION_1

SG-CLK=M,24,0

SG-SCREEN1=4.6; SG-SCREEN2=1.5.6; SG-SCREEN3=4.3.1; SG-SCREEN4=1.1

SG-SCREEN5=3.2; SG-SCREEN6=3.5; SG-SCREEN7=0; SG-SCREEN8=0

SG-SCREEN9=0; SG-SCREEN10=0; SG-SCREEN11=0; SG-SCREEN12=0

SG-SCREEN13=0; SG-SCREEN14=0; SG-SCREEN15=0; SG-SCREEN16=0

SG-COM0=9600,A0,P0,R1,X1

SG-COM2=9600,A0,P0,R1,X0,MF1,MPN,MR10,MS1,PW0

SN Command
Purpose:

Read/Set User Programmable Names

Syntax:

SN[-{var}[={name},{TRUE label},{FALSE label}]

Example:

SN or SN-VO1=TRIP,CLOSED,OPEN or SN-IN1=BREAKER,OPEN,CLOSED

SN Command Example:

Example 1.

Read the programmed labels for the alarm output (OUTA).

>SN-VOA

SN-VOA=VOA_LBL,TRUE,FALSE

S<g> Command
Purpose:

Read all Protection settings

Syntax:

S{g} where g=setting group 0-1 or # for all groups

Example:

S# or S0 or S1

S <g> Command Example:

Example 1.

Obtain a list of settings for Setting Group 1.

>S1

S1-50TP=0.00, 0m,N

S1-50TN=0.00, 0m,N

S1-50TQ=0.00, 0m,N

S1-150TP=0.00, 0m,N

S1-150TN=0.00, 0m,N

S1-150TQ=0.00, 0m,N

S1-51P=0.00,0.0,V2,N

S1-51N=0.00,0.0,V2,N

11-6

BE1-700 ASCII Command Interface

9376700990 Rev M