Reclosing fail timer (79f) -52, Maximum cycle timer (max cycle) -52, Sequence controlled blocking (scb) -52 – Basler Electric BE1-700 User Manual

Page 108: Table 4-30. operating settings for reclosing -52

Advertising
background image

Table 4-30. Operating Settings for Reclosing

Setting

Range

Increment

Default

Time

Delays

0.1 to 600 seconds

0.001 second (0 to 0.999 seconds)

0.1 second (1.0 to 9.9 seconds)

1 second (10 to 600 seconds)
0.1 cycles (6 to 36000 cycles)

791 = 0

792 = 0

793 = 0

794 = 0

79R = 10s

79F = 1s

79M = 60s

79P = 0

Step List

1. 79SCB TRUE during Reset and while timing to Reset after

Lockout.

2. 79SCB TRUE when 79C is TRUE for first reclose and

while timing to Reset after first reclose.

3. 79SCB TRUE when 79C is TRUE for second reclose and

while timing to Reset after second reclose.

4. 79SCB TRUE when 79C is TRUE for third reclose and

while timing to Reset after third reclose.

5. 79SCB TRUE when 79C is TRUE for fourth reclose and

while timing to Reset after fourth reclose.

0

Reclosing Fail Timer (79F)

This timer begins when the 79C output becomes TRUE and continues counting until the STATUS input
becomes TRUE. If the 79F timer times out, the recloser function is driven to lockout and the 79LO output
becomes TRUE. The relay remains in Lockout until the breaker is manually closed and the STATUS input
remains TRUE for the reset time. This setting can be changed on the Reclosing screen in BESTCOMS.
See Figure 4-50.

Maximum Cycle Timer (MAX Cycle)

Max Cycle is the reclose maximum operation time. If a reclose operation is not completed before the
maximum operate time expires, the recloser goes to Lockout. This timer limits the total fault clearing and
restoration sequence to a definable period. The timer starts when the first trip command is issued from a
protective element of the relay. The Max Cycle timer stops when the recloser is reset. If the total reclosing
time between Reset states exceeds the maximum reclose cycle timer setting, the recloser will go Lockout.
If the WAIT input goes high during the Max Cycle timing sequence, Max Cycle timing will “pause” until the
WAIT input goes low. If not desired, the Max Cycle timer can be disabled by setting it at zero. This setting
can be changed on the Reclosing screen in BESTCOMS. See Figure 4-50.

Sequence Controlled Blocking (SCB)

The 79SCB output is TRUE when the breaker is closed, the 79 close output (79C) is TRUE, and the
reclose sequence step is enabled with a non-zero value. A 0 (zero) disables the 79SCB output. This
setting can be changed on the Reclosing screen in BESTCOMS by checking the appropriate Trip box.
See Figure 4-50.

Figure 4-51 shows a logic timing diagram showing all possible sequence controlled blocks enabled
(TRUE). In Figure 4-52, 79RTD is the reclose reset time delay and 79#TD is the reclose time delay where
# is the reclose shot number.

4-52

BE1-700 Protection and Control

9376700990 Rev M