Basler Electric BE1-700 User Manual

Page 195

Advertising
background image

Table 8-7. 700C-OC79-A-BE (OC with 79) Function Block Logic

Function

Purpose

BESTlogic

Expression

Mode Setting

50TP

Block when recloser sequence controlled blocking output
is TRUE.

79SCB

1 (enabled)

50TN

Block when recloser sequence controlled blocking output
is TRUE or when disabled by IN4.

79SCB+/IN4

1 (3-ph residual)

50TQ

Block when recloser sequence controlled blocking output
is TRUE or when disabled by IN4.

79SCB+/IN4

1 (enabled)

150TP

Used for high set

0

1 (enabled)

150TN

Used for high set

0

1 (3-ph residual)

150TQ

Used for high set

0

1 (enabled)

51P

Used for phase TOC protection

0

1 (enabled)

51N

Used for neutral TOC protection. Disabled when IN4 is low

/IN4

1 (3-ph residual)

51Q

Used for negative-sequence TOC protection. Disabled
when IN4 is low

/IN4

1 (enabled)

151N

Not used

0

0 (disabled)

62

Not used

0

0 (disabled)

162

Not used

0

0 (disabled)

79

Reclose Initiate: Initiates reclosing sequence when RI is
TRUE.

VO8

1

(Power Up to

Lockout)

Breaker Status Logic: Closed breaker is indicated when
IN1 is de-energized.

Wait Logic: Stop recloser timing when timing for a fault
trip. TRUE when protection picked up expression is TRUE.

Block/Drive to Lockout Logic: Drive recloser to lockout
when external recloser on/off switch is off.

Pilot Initiate: Initiate one high speed reclose when PI is
TRUE

/IN1

VO12

VO9

0

BF

Not used

0

0 (disabled)

9376700990 Rev M

BE1-700 Application

8-13