Basler Electric BE1-700 User Manual

Page 88

Advertising
background image

Operating settings are made using BESTCOMS. Figure 4-27 illustrates the BESTCOMS screen used to
select operational settings for the auxiliary Under/Overvoltage element. To open the Voltage Protection
screen for Under/Overvoltage elements, select Voltage Protection from the Screens pull-down menu.
Then select either the 27X or the 59X/159X tab. Alternately, settings may be made using the S<g>-59X,
S<g>-159X, and S<g>-27X ASCII commands or through HMI Screens 5.x.3.2 (27x), 5.x.8.2 (59x), and
5.x.8.4 where x equals 1 (Setting Group 0) or 2 (Setting Group 1).

Beside the Logic pull-down menu is a pull-down menu labeled Settings. The settings menu is used to
select the setting group that the elements settings apply to.

Figure 4-27. Voltage Protection Screen, 59X/159X Tab

Table 4-20 summarizes the operating settings for Auxiliary Undervoltage/Overvoltage Protection.

Table 4-20. Operating Settings for Auxiliary Undervoltage/Overvoltage Protection

Setting

Range

Increment

Unit of Measure

Default

Pickup

0 = Disabled

1 to 150

0.1 for 0 to 99.9

1.0 for 100 to 150

Secondary Volts

0

Inhibit

27X only

0 = Disabled

1 to 150

0.1

Secondary Volts

0

Time Delay

50 to 999 milliseconds

1

Milliseconds

50 ms

1 to 600 seconds

0.1 for 1.0 to 9.9

Seconds

1.0 for 10 to 600

Seconds

3 to 36,000 cycles (60 Hz)

Cycles

2.5 to 30,000 cycles (50 Hz)

∗ Time delays less than 10 cycles can be entered to the nearest 0.1 cycles from the front panel HMI. All
time delays can be entered to the nearest 0.01 cycles from the ASCII command interface. Time delays
entered in cycles are converted to milliseconds or seconds. Increment precision after conversion is limited
to that appropriate for each of those units of measure.

4-32

BE1-700 Protection and Control

9376700990 Rev M

Advertising
This manual is related to the following products: