Basler Electric BE1-700 User Manual

Page 204

Advertising
background image

Output

Purpose

Description

Label

State Labels

BESTlogic expression:
VO2=24T+27PT+127PT+27XT+47T+59PT+159PT+59XT+159XT+81T+181T+281T+381T+481T+581T

VO3
(OUT3)

Not used

VO3

True

False

BESTlogic expression: VO3=0

VO4
(OUT4)

Not used

VO4

True

False

BESTlogic expression: VO4=0

VO5
(OUT5)

Not used

VO5

True

False

BESTlogic expression: VO5=0

VO6

Not used

VO6

True

False

BESTlogic expression: VO6=0

VO7

Not used

VO7

Trip

Normal

BESTlogic expression: VO7=0

VO8

Not used

VO8

True

False

BESTlogic expression: VO8=0

VO9

Not used

VO9

True

False

BESTlogic expression: VO9=0

VO10

Not used

VO10

True

False

BESTlogic expression: VO10=0

VO11

Protective trip expression

VO11 is TRUE when any
OC&P or V&F protection
element trips

PROT_TRIP

Trip

Normal

BESTlogic expression:
VO11=24T+27XT+27PT+127PT+47T+59PT+159PT+59XT+159XT+81T+181T+281T+381T+481T+581T

VO12

Protective pickup
expression

VO12 is TRUE when any
protection element picks up

PROT_PU

PU

Normal

BESTlogic expression: VO12=24PPU+27XPU+27PPU+127PPU+47PU+59PPU+159PPU
+59XPU+159XPU+81T+181T+281T+381T+481T+581T

VO13

Alarm Mask 21

VO13

True

False

BESTlogic expression: VO13=0

VO14

Alarm Mask 22

VO14

True

False

8-22