S<g>-47 Command (BE1-700V only)
Purpose:

Read/Set 47 pickup level and time delay

Syntax:

S{g}-47[={pu(V)},{td(m)}] where g=0,1

Example:

S0-47 or S1-47=100,0

Reference:

Section 4, Protection and Control, Voltage Protection

S<g>-50T Command (BE1-700C only)
Purpose:

Read/Set 50T pickup level and time delay

Syntax:

S{g}-{x}50T[{p}][={pu(A)},{td(m)}] where g=0,1, x=blank/1, and p=P/N/Q

Example:

S0-50T or S1-50TP=25,0 or S1-150TN=3,20

Reference:

Section 4, Protection and Control, Overcurrent Protection

S<g>-51 Command (BE1-700C only)
Purpose:

Read/Set 51 pickup level, time delay, curve, and direction

Syntax:

S{g}-51[{p}][={pu(A)},{td(m)},{crv},{dir}] where g=0,1 and p=P/Q

Example:

S0-51P or S0-51P=7.5,6.5,S1,N or S1-51Q=3,2.0,S1,F

Reference:

Section 4, Protection and Control, Overcurrent Protection

S<g>-51N Command (BE1-700C only)
Purpose:

Read/Set 51N pickup level, time delay and curve

Syntax:

S{g}-{x}51N[={pu(A)},{td(m)},{crv},{dir}] where x=blank/1 and g=0,1

Example:

S0-51N or S0-51N=7.5,6.5,S1,N or S1-151N=3,2.0,S1,F

Reference:

Section 4, Protection and Control, Overcurrent Protection

S<g>-59 Command (BE1-700V only)
Purpose:

Read/Set 59 pickup level and time delay

Syntax:

S{g}-59[{p}][={pu(V)},{td(m)}] where g=0,1 and p=P/X

Example:

S0-59P or S1-59P=100,0 or S1-59X=80,20 S1-159X=80,20

Reference:

Section 4, Protection and Control, Voltage Protection

S<g>-62 Command
Purpose:

Read/Set 62 Time Delay

Syntax:

S{g}-{x}62[={t1},{t2}] where g=0,1 & t suffix m=msec,s=sec,c=cycle

Example:

S0-62=500m,200m or S0-62=0.5s,0.2s or S1-162=30c,12c

Reference:

Section 4, Protection and Control, General Purpose Logic Timers

S<g>-79 Command (Optional)
Purpose:

Read/Set 79 Time Delay

Syntax:

S{g}-79[#][={td}] where g=0,1 & t suffix m=msec,s=sec,c=cy

Example:

S0-791=100m or S0-792=0.5s or S0-793=60c

Reference:

Section 4, Protection and Control, Reclosing

S<g>-79SCB Command
Purpose:

Read/Set 79 Sequence Controlled Block Output

Syntax:

S{g}-79SCB[={step list}] where g=0,1

Example:

S0-79SCB=2/4

Reference:

Section 4, Protection and Control, Reclosing

S<g>-81 Command (BE1-700V only)
Purpose:

Read/Set 81 pickup level, time delay, and mode

Syntax:

S{g}-{x}81[={pu(Hz)},{td(m)},{mode}] where g=0,1 and x=blank/1/2/3/4/5

Example:

S0-81 or S0-81=59.00,6.5,U or S1-81=60.50,2.0,O or S1-81=0.2,0,R

Reference:

Section 4, Protection and Control, Frequency Protection

11-20

BE1-700 ASCII Command Interface