Table b-4), Table b-5), M (table b-6) – Basler Electric BE1-700 User Manual

Page 442

Advertising
background image

Table B-4. Report Commands

Type

ASCII Command

Function

HMI

Screen

RA[=0]

Report/Reset alarm information.

1.3

RA-LGC[=0]

Report/Reset logic alarm information.

N/A

RA-MAJ[=0]

Report/Reset major alarm information.

N/A

RA-MIN[=0]

Report/Reset minor alarm information.

N/A

RA-REL[=0]

Report/Reset relay alarm information.

N/A

RB

Read breaker status.

1.5.6

C

RB-DUTY[<phase>[=%duty>]

Read/Set breaker contact duty log.

4.3.2

RB-OPCNTR[=<#operations>]

Read/Set breaker operation counter.

4.3.1

C

RD

Report all demand data.

N/A

C

RD-PI<p>[=0]

Read/Reset peak demand current.

4.4.3.1 -

4.4.3.5

C

RD-TI[<p>]

Report today’s demand current.

4.4.1.1 -

4.4.1.5

C

RD-YI[<p>]

Report yesterday’s demand current.

4.4.2.1 -

4.4.2.5

RF[-n/NEW][=0/TRIG]

Read/Reset fault report data.

N/A

RG

Report general information.

N/A

RG-DATE[={M/D/Y}] or RG-
DATE[={D-M-Y}]

Read/Set date.

4.6

RG-DST

Report Start/Stop Times and Dates for Daylight
Savings Time referenced to local time.

N/A

RG-STAT

Report relay status.

N/A

RG-TARG[=0]

Report/Reset target status.

1.2

RG-TIME[=hr:mn:sc] or RG-
TIME[=hr:mn<f>sc]

Report/Set time.

4.6

RG-VER

Read program version, model number, style
number, and serial number.

4.7

RO-nA/B[#].CFG/DAT

Read oscillographic COMTRADE fault report.

N/A

RS[-n/Fn/ALM/IO/LGC/NEW][=0]

Read/Reset Sequence of Events Record Data.

N/A

Table B-5. Setting Command

Type

ASCII Command

Function

HMI Screen

S

Read all relay setting parameters.

N/A

Table B-6. Alarm Setting Commands

Type

ASCII Command

Function

HMI Screen

SA

Read all major and minor alarm setting.

N/A

V

SA-24[=<alarm level>,time delay>]

Read/Set Volts Per Hertz alarm settings.

N/A

SA-BKR<n>[=<mode>,<alarm limit>]

Read/Set breaker alarm settings.

N/A

SA-DI<p>[=<alarm level>]

Read/Set demand alarm settings.

N/A

SA-LGC[=<alarm num 1>[/<alarm num 2>]…
[<alarm num n>]]

Read/Set logic alarm setting mask.

N/A

SA-MIN[=<alarm num 1>[/<alarm num 2>]…
[<alarm num n>]]

Read/Set minor alarm setting mask.

N/A

SA-MAJ[=<alarm num 1>[/<alarm num 2>]…
[<alarm num n>]]

Read/Set major alarm setting mask.

N/A

SA-RESET[=<rst alm logic>]

Read/Set programmable alarms reset logic.

N/A

B-2

BE1-700 Command Cross-Reference

9376700990 Rev M