Example 1.

Turn off the hold timer for Output 1:

SG-HOLD1=0
SG-HOLD2=0


Set the timer logic:

SL-62=1,IN1,1,0


Set the pickup and dropout times:

S#-62=2C,2C


Set the output logic:

VO1=101T+BFPU+VO11+VO6
VO2=101C+79C+VO7
VO6=VO1*/162
VO7=VO2*62

NOTE

The following example is based on the 700C logic scheme.

8-42

BE1-700 Application

9376700990 Rev M