Style Number. This line reports the style number of the relay.

Serial Number. This line reports the serial number of the relay.

Firmware Version. This line reports the version of firmware that the relay holds.

Station ID and Relay ID. These lines report station and device identifier information as defined by the SG-
ID command.

Relay Address. This line reports the communications port address that the report was requested from.
The relay address number is assigned using the SG-COM command, described in Section 11, ASCII
Command Interface
.

Fault Number. This line reports the sequential number (from 1 to 255) assigned to the report by the BE1-
700.

Fault Type. This line reports the type of fault that occurred. There are five fault type categories:

• Trip: A fault was detected as defined by the pickup expression and the relay tripped to clear the

fault.

• Pickup: A fault was detected as defined by the pickup expression but the relay never tripped

indicating that the fault was cleared by another device.

• Logic: A fault report was recorded by the logic trigger expression but no fault was detected as

defined by the pickup expression.

• Breaker Failure: A fault was detected as defined by the pickup expression and the breaker failure

trip became TRUE before the fault was cleared.

• RF=TRIG: A fault report was recorded by the ASCII command interface.

Fault Date and Time. These lines report the date and time of the initial trigger of the event. This is based
on either the pickup logic expression or the logic trigger expression becoming TRUE as defined by the
SG-TRIGGER command. Refer to Figure 6-6 and Table 6-9, call-out A.