SL-VO Command
Purpose:

Read/Set Output Logic

Syntax:

SL-VO[#[={Boolean equation}]]

Example:

SL-VO or SL-VO1=50TPT+50TNT+51PT+51NT+101T

Reference:

Section 7, BESTlogic Programmable Logic, Working With Programmable Logic

User Programmable Name Setting Command

SN Command
Purpose:

Read/Set User Programmable Names

Syntax:

SN[-{var}[={name},{TRUE label},{FALSE label}]

Example:

SN or SN-VO1=TRIP,CLOSED,OPEN or SN-IN1=BREAKER,OPEN,CLOSED

Reference:

Section 7, BESTlogic Programmable Logic, User Input and Output Logic Variable Names

Protection Setting Commands

S<g> Command
Purpose:

Read all Protection settings

Syntax:

S{g} where g=setting group 0-1 or # for all groups

Example:

S# or S0 or S1

Reference:

Section 11, ASCII Command Interface, Settings (S) Command Descriptions

S<g>-24 Command (BE1-700V only)
Purpose:

Read/Set 24 pickup level, time delay, reset delay and curve

Syntax:

S{g}-24[={pu(V/Hz)},{td},{rst},{crv}] where g=0,1

Example:

S0-24 or S0-24=2.5,6.5,9.9,2 or S1-24=3,2.0,5.0,1

Reference:

Section 4, Protection and Control, Voltage Protection

S<g>-24D Command (BE1-700V only)
Purpose:

Read/Set 24 definite time pickup levels and time delays

Syntax:

S{g}-24D[={pu1(V/Hz)},{td1},{pu2(V/Hz)},{td2}] where g=0,1

Example:

S0-24D or S0-24D=1.1,6000,1.18,45000 or S1-24D=1.12,8000,1.20,60000

Reference:

Section 4, Protection and Control, Voltage Protection

S<g>-25 Command (BE1-700V only)
Purpose:

Read/Set 25 delta volts, phase angle, slip freq and mode

Syntax:

S{g}-25[={Volts},{Ang},{Slip},{mode}] where g=0,1, mode=1-PF>XF, 0-PF<>XF

Example:

S0-25 or S0-25=5,3,0.1,0 or S1-27=2,5,0.25,1

Reference:

Section 4, Protection and Control, Synchronism-Check Protection

S<g>-25VM Command (BE1-700V only)
Purpose:

Read/Set 25VM live volts, dead volts, time delay, and VM1 logic

Syntax:

S{g}-25VM[={LV},{DV},{td},{VM1}] where g=0,1, VM1=DIS/123

Example:

S0-25VM or S0-25=80,20,100,123 S1-25VM=80,20,0.25,23

Reference:

Section 4, Protection and Control, Synchronism-Check Protection

S<g>-27 Command (BE1-700V only)
Purpose:

Read/Set 27 pickup level, time delay, and inhibit level

Syntax:

S{g}-{x}27{p}[={pu(V)},{td(m)},{inh(V)}] where x= blank/1, g=0,1, p=P,X

Example:

S0-27P or S0-27P=100,10s,20, S0-27X=100,10s,20, S0-127P=80,5s,20

Reference:

Section 4, Protection and Control, Voltage Protection

9376700990 Rev M

BE1-700 ASCII Command Interface

11-19