24 overexcitation protection (be1-700v), 25 sync-check protection (be1-700v, optional), 24 overexcitation protection (be1-700v) -7 – Basler Electric BE1-700 User Manual

Page 19: 25 sync-check protection (be1-700v, optional) -7

Advertising
background image

24 Overexcitation Protection (BE1-700V)

Pickup

Setting Range:

0.5 to 6 V/Hz

Accuracy:

±2%

Integrating Time Delay

Time Dial:

0.0 to 9.9

Reset Dial:

0.0 to 9.9

Accuracy:

5% or 4 cycles, whichever is greater

n

NOMINAL

MEASURED

T

1

HZ

V

HZ

V

DT

T

=

Time to Trip

100

*

FST

E

*

D

T

T

R

R

=

Time to Reset

where:

T

T

= Time to trip

T

R

= Time to reset

D

T

= Time dial trip

D

R

= Time dial, reset

E

T

= Elapsed time

n = Curve exponent (0.5, 1, 2)

FST = Full scale trip time (TT)

ET/FST = Fraction of total travel toward trip that integration had progressed to. (After a trip,

this value will be equal to one.)

Definite Time Delay

Time Delay:

0.050 to 600 s

Accuracy:

5% or 4 cycles, whichever is greater

25 Sync-Check Protection (BE1-700V, Optional)

Settings

Delta Phase Angle:

1 to 99

°

Accuracy:

±0.5°

Delta Voltage Magnitude:

1 to 20 V

Accuracy:

±2% or ±1 V, whichever is greater

Delta Frequency:

0.01 to 0.50 Hz

Accuracy:

±0.01 Hz

Voltage Monitoring

Live/Dead voltage threshold:

10 to 150 V

Accuracy:

±2% or ±1 V

Dropout Time delay:

0.050 to 60 s

Accuracy:

±0.5% or ±2 cycles, whichever is greater

Logic:

Dead Phase/Dead Aux
Dead Phase/ Live Aux
Live Phase/ Dead Aux

One independent output:

25VM1

9376700990 Rev M

BE1-700 General Information