Time overcurrent characteristic curve graphs – Basler Electric BE1-700 User Manual

Page 418

Advertising
background image

Table A-1. 51P, 51N, and 51Q Time Characteristic Curve Constants

Curve

Selection

Curve Name

Trip Characteristic Constants §

Reset

A

B

C

N

K

R

S1

S, S1, Short Inverse

0.2663

0.03393

1.0000

1.2969

0.0280

0.5000

S2

S2, Short Inverse

0.0286

0.02080

1.0000

0.9844

0.0280

0.0940

L1

L, L1, Long Inverse

5.6143

2.18592

1.0000

1.0000

0.0280

15.750

L2

L2, Long Inverse

2.3955

0.00000

1.0000

0.3125

0.0280

7.8001

D

D, Definite Time

0.4797

0.21359

1.0000

1.5625

0.0280

0.8750

M

M, Moderately Inverse

0.3022

0.12840

1.0000

0.5000

0.0280

1.7500

I1

I, I1, Inverse Time

8.9341

0.17966

1.0000

2.0938

0.0280

9.0000

I2

I2, Inverse Time

0.2747

0.10426

1.0000

0.4375

0.0280

0.8868

V1

V, V1, Very Inverse

5.4678

0.10814

1.0000

2.0469

0.0280

5.5000

V2

V2, Very Inverse

4.4309

0.09910

1.0000

1.9531

0.0280

5.8231

E1

E, E1, Extremely Inverse

7.7624

0.02758

1.0000

2.0938

0.0280

7.7500

E2

E2, Extremely Inverse

4.9883

0.01290

1.0000

2.0469

0.0280

4.7742

A

A, Standard Inverse

0.01414

0.00000

1.0000

0.0200

0.0280

2.0000

B

B, Very Inverse (I

2

t)

1.4636

0.00000

1.0000

1.0469

0.0280

3.2500

C

C, Extremely Inverse (I

2

t)

8.2506

0.00000

1.0000

2.0469

0.0280

8.0000

G

G, Long Time Inverse (I

2

t)

12.1212

0.00000

1.0000

1.0000

0.0280

29.0000

F

Fixed Time

0.0000

1.00000

0.0000

0.0000

0.0280

1.0000

P

Programmable

0 to 600

0 to 25

0 to 1

0.5 to 2.5

0.0280

0 to 30

46

Neg.-Seq. Overcurrent

0

0

2

0.0280

100


∗ Curve F has a fixed delay of one second times the Time Dial setting.

† For integrated reset, append R to the curve name. For example, curve S1 has instantaneous reset.

Curve S1R has integrated reset.

‡ Constant A is variable for the 46 curve and is determined, as necessary, based on system full-load

current setting, minimum pickup, and K factor settings.

§ The programmable curve allows for four significant digits after the decimal place for every variable.

TIME OVERCURRENT CHARACTERISTIC CURVE GRAPHS

Figures A-1 through A-16 illustrate the characteristic curves of the BE1-700 relay. Table A-2 cross-
references each curve to existing electromechanical relay characteristics. Equivalent time dial settings
were calculated at a value of five times pickup.

A-2

BE1-700 Time Overcurrent Characteristic Curves

9376700990 Rev M