Setting command, Alarm setting commands, Setting command -13 – Basler Electric BE1-700 User Manual

Page 259: Alarm setting commands -13

Advertising
background image

RS Command
Purpose:

Read/Reset Sequence of Events Record Data

Syntax:

RS[-n/Fn/ALM/IO/LGC/NEW][=0] where n=# of events and Fn=fault record #

Example:

RS (displays a directory of all event records in memory)

RS-23 (view SER report for last 23 events)

RS-F12 (view SER report associated with fault record 12)

RS-ALM (view all SER report ALARM events since RS=0 reset)

RS-IO (view all SER report INPUT OUTPUT events since RS=0 reset)

RS-LGC (view all SER report LOGIC events since RS=0 reset)

RS-NEW (view all SER report events since RS=0 reset)

RS=0 (reset NEW records counter)

Reference:

Section 6, Reporting and Alarm Functions, Sequence of Events Recorder

Setting Command

S Command
Purpose:

Read all relay setting parameters

Syntax:

S

Example:

S

Reference:

Section 11, ASCII Command Interface, Settings (S) Command Descriptions

Alarm Setting Commands

SA Command
Purpose:

Read all alarm settings for Major and Minor alarms

Syntax:

SA

Example:

SA

Reference:

Section 6, Reporting and Alarm Functions, Alarms Function

SA-24 Command (BE1-700V only)
Purpose:

Read/Set Volts Per Hertz alarm settings

Syntax:

SA-24[={alarm level},{td(m)}] alarm level=volts per hertz

Example:

SA-24 or SA-24=1.1,2000 or SA-24=1.08,500

Reference:

Section 4, Protection and Control, Voltage Protection

SA-BKR Command
Purpose:

Read/Set breaker alarm settings

Syntax:

SA-BKR[n][={mode},{alarm limit}] where mode=0-3(disabled/%duty/#op/clr)

Example:

SA-BKR or SA-BKR1=1,80 or SA-BKR2=2,250, or SA-BKR3=3,6c

Reference:

Section 6, Reporting and Alarm Functions, Breaker Monitoring

SA-DI Command
Purpose:

Read/Set demand alarm settings

Syntax:

SA-DI[p][={alarm level}] where p=P/N/Q, alarm level=Sec Amps

Example:

SA-DI or SA-DIP=0 or SA-DIN=10

Reference:

Section 6, Reporting and Alarm Functions, Demand Functions

SA-LGC Command
Purpose:

Read/Set logic alarm setting mask

Syntax:

SA-LGC[={alarm num 1}[/{alarm num 2}]...[/{alarm num n}]]

Example:

SA-LGC or SA-LGC=2/6/7/10/11

Reference:

Section 6, Reporting and Alarm Functions, Alarms Function

9376700990 Rev M

BE1-700 ASCII Command Interface

11-13