SL-51Q Command (BE1-700C only)
Purpose:

Read/Set Logic for 51Q Function Modules

Syntax:

SL-51Q[={mode},{BLK logic}]

Example:

SL-51Q or SL-51Q=1,0 or SL-51Q=1,IN3

Reference:

Section 4, Protection and Control, Overcurrent Protection

SL-101 Command
Purpose:

Read/Set Logic for Virtual Breaker switch (101)

Syntax:

SL-101[=mode] where mode=0/1 (disabled/enabled)

Example:

SL-101 or SL-101=0 or SL-101=1

Reference:

Section 4, Protection and Control, Virtual Switches

SL-59 Command (BE1-700V only)
Purpose:

Read/Set Logic for 59 Function Modules

Syntax:

SL-59[{p}[={mode},{BLK logic}]] where p=P/X

Example:

SL-59 or SL-59P=1,0 or SL-59X=2,0 or SL-159X=1,IN3

Reference:

Section 4, Protection and Control, Voltage Protection

SL-62 Command
Purpose:

Read/Set Logic for 62 Function Modules

Syntax:

SL-{x}62[={mode},{INI logic},{BLK logic}] where x=blank/1

Example:

SL-62 or SL-62=1,VO10,0 or SL-162=2,VO9,VO8

Reference:

Section 4, Protection and Control, General Purpose Logic Timers

SL-79 Command (Optional)
Purpose:

Read/Set for 79 Function

Syntax:

SL-79[={mode},{RILogic},{STATUSLogic},{WAITLogic},{LOCKOUTLogic},{PILOTLogic}]

Example:

SL-79 or SL-79=1,VO1+IN4,/IN1,IN2,IN3

Reference:

Section 4, Protection and Control, Reclosing

SL-81 Command (BE1-700V only)
Purpose:

Read/Set Logic for 81 Function Modules

Syntax:

SL-{x}81[={mode},{BLK logic}] where mode=0/1/X, x=blank/1/2/3/4/5

Example:

SL-81 or SL-81=1,0 or SL-81=X,0 or SL-181=1,IN3

Reference:

Section 4, Protection and Control, Frequency Protection

SL-BF Command (BE1-700C only)
Purpose:

Read/Set Logic for Breaker Failure Function Modules

Syntax:

SL-BF[{p}[={mode},{INI logic},{BLK logic}]]

Example:

SL-BF or SL-BF=1,VO1,0 or SL-BF=1,VO1,IN1

Reference:

Section 4, Protection and Control, Breaker Failure Protection

SL-GROUP Command
Purpose:

Read/Set Logic for Setting Group Module

Syntax:

SL-GROUP[={mode},{D0Logic},{D1Logic},{AUTOlogic}]

Example:

SL-GROUP or SL-GROUP=1,0,IN3,0

Reference:

Section 4, Protection and Control, Setting Groups

SL-N Command
Purpose:

Read/Set Name of the custom logic

Syntax:

SL-N[={name}]

Example:

SL-N=700TEST

Reference:

Section 7, BESTlogic Programmable Logic, Logic Schemes

11-18

BE1-700 ASCII Command Interface

9376700990 Rev M