Relay Equation

When the 46 function is used, the relay uses the K factor (i.e., 46 time dial setting), 46 minimum pickup
setting and generator full-load current to create a constant Z (see Equation A-4).

2

Setting

Nom

Setting

Pickup

46

I

Dial

Time

46

Z



=

Equation A-4

The time to trip equation used in the relay is:

seconds

0.028

M

Z

T

2

T

+

=

Equation A-5

where

Setting

Pickup

46

I

Measured

M

2

=

Equation A-6

which, when M > 1, reduces to:

2

2

Setting

Nom

T

Measured

I

I

Dial

Time

46

T



=

Equation A-7

9376700990 Rev M

BE1-700 Time Overcurrent Characteristic Curves