Basler Electric BE1-700 User Manual

Page 208

Advertising
background image

Figure 8-10. 700V-VF79-A-BE (V & F Protection with Reclosing) One-Line Drawing

Table 8-16. 700V-VF79-A-BE (V & F Protection with Reclosing) Contact Sensing Input Logic

Input

Purpose

Label

State Labels

Energized

De-Energized

IN1

Breaker status indication in Sequence of
Events Reporting. TRUE when breaker is
open. Typically, IN1 is connected to the 52b
contact of the breaker.

BREAKER

OPEN

CLOSED

IN2

Reclosing Drive to Lockout. Drives recloser
to lockout when external switch is turned off.
Contact from external switch must be closed
in the off position, open in the on.

REC_OFF

OFF

ON

IN3

External time delay reclose initiate. TRUE
when RI is high.

EXT_RI

ACTIVE

NORMAL

IN4

External high speed (pilot) reclose initiate.
TRUE when PI is high.

EXT_PI

ACTIVE

NORMAL

Table 8-17. 700V-VF79-A-BE (V & F Protection with Reclosing) Function Block Logic

Function

Purpose

BESTlogic

Expression

Mode Setting

24

Used for detection of transformer overexcitation

0

1 (enabled)

25

(25VM)

Blocked when 79C is FALSE (/79C) or when 79LO is
TRUE. Set 25VM Hot Bus-Dead Line

/79C+79LO

1 (enabled)

8-26

BE1-700 Application

9376700990 Rev M