Commissioning testing, Digital i/o connection verification, Commissioning testing -8 – Basler Electric BE1-700 User Manual

Page 304: Digital i/o connection verification -8

Advertising
background image

bus voltage by 30 degrees, the sign of the angle will be negative or –30 degrees. When the line
voltage leads, the angle has no sign and is assumed to be positive.

• Return the line voltage angle to 0 degrees. Vary the frequency of the line voltage and verify the

measured slip as in Step 3. (Note that the angle shown on HMI Screen 3.11 is continuously
changing as a result of slip between the two systems. This is normal). Polarity of the slip
frequency is relative to the frequency of the line. That is, if the line frequency is 58 hertz and the
bus frequency is 60 hertz, the slip frequency is –2. As soon as the line frequency rises above 60
hertz, slip frequency has no sign and is assumed to be positive.

COMMISSIONING TESTING

Because the commissioning of this relay may be a new installation or a retrofit, special precautions should
be taken to ensure that all tests are performed with safety as the utmost concern. Any CT circuit signals
that are routed through this device as part of a protection scheme including discrete relays or as a stand-
alone device should be shorted and isolated from this relay during these tests until the final instrument
transformer current circuit check.

If this relay is being installed in an existing installation, please be aware of the equipment monitoring
features of this device, especially if the monitoring logic will be utilized. Please make note of any pretest
operation levels, duty levels, etc. on existing equipment (e.g., breakers or transformers). As the user, you
may make the determination of what values the relay should have as initial monitoring values when the
relay is placed in service.

Also, please be aware that because of the multi-function nature of the BE1-700 relay, it may on occasion
be necessary to temporarily disable some of the protective elements while testing the relay to facilitate
isolated testing of individual functions. Always remember to enable these functions before placing the
relay in service.

To assist you in the commissioning testing of this relay, you may at any time refer to Section 6, Reporting
and Alarm Functions
, for various means of reporting status, alarms, and targets.

Please refer to the other sections of this instruction manual for assistance on any particular functions of
the relay. If you require further assistance, contact Basler Electric field application personnel or the
factory.

Digital I/O Connection Verification

Contact Sensing Inputs

Purpose: To verify contact sensing input label assignments and recognition and debounce settings.

Reference Commands: SN-IN, SG-IN

Step 1: Transmit the SN-IN1 command to verify the Input 1 user-defined name, Energized State label,

and De-Energized State label.

Step 2: Repeat Step 1 for each of the remaining contact sensing inputs. Add the number of an input to

the SN-IN command to check that input's name and labels.

Step 3: Verify the recognition and debounce settings for each contact sensing input by using the SG-IN

command. When the SG-IN command is transmitted, the relay responds with the recognition
and debounce settings for each input. Reported settings use the format SG-IN#=recognition,
debounce.

Step 4: Transmit the RG_STAT command to the relay or use HMI Screen 1.4.1 to verify the status of

Input 1. Transmit the RS-NEW=0 command to the relay. From the actual field device, energize
(or de-energize) the specific contact that supplies relay Input 1. While maintaining contact
position, verify that Input 1 has changed state by transmitting the RG-STAT command or using
HMI Screen 1.4.1. Return the field contact to its original state, verifying that Input 1 returns to its
original state. Transmit the RS-NEW command to the relay and review the event record
associated with the field contact change.

Step 5: Repeat Step 4 for each connected input.

Output Contacts

Purpose: To verify output contact settings and output contact logic settings.

Reference Commands: SN-VO, SL-VO, SG-HOLD

13-8

BE1-700 Testing and Maintenance

9376700990 Rev M