Basler Electric BE1-700 User Manual

Page 261

Advertising
background image

SG-CLK Command
Purpose:

Read/Program format of date and time display

Syntax:

SG-CLK[={date format(M/D)},{time format(12/24)},{dst enable(0/1)}]

Example:

SG-CLK=D,12,1 or SG-CLK=M,24,0

Reference:

Section 6, Reporting and Alarm Functions, Clock

SG-COM Command
Purpose:

Read/Set serial communications protocol

Syntax:

SG-COM[#[={baud},A{addr},P{pglen},R{reply ack},X{XON ena}]]

Example:

SG-COM0=9600 or SG-COM0=9600,A0,P24,R1,X1

Reference:

Section 11, ASCII Command Interface, Settings (S) Command Descriptions, Configuring
the Serial Port Communication Protocol

SG-CT Command (BE1-700C only)
Purpose:

Read/Set Phase/Neutral CT ratio

Syntax:

SG-CT[t][={CTratio}] where t = P/G

Example:

SG-CTP=80 or CTG=400:5 or CTG=400/5

Reference:

Section 3, Input and Output Functions, Power System Inputs

SG-DI Command (BE1-700C only)
Purpose:

Read/Set P(IA/IB/IC), N and Q demand interval

Syntax:

SG-DI[p][={interval}] where p=P/N/Q, interval=0-60 (min)

Example:

SG-DI or SG-DIP=15 or SG-DIN=1

Reference:

Section 6, Reporting and Alarm Functions, Demand Functions

SG-DSP Command
Purpose:

Read analog signal dsp filter type

Syntax:

SG-DSP[P/N] F=fundamental

Example:

SG-DSP, SG-DSPP, SG-DSPN

Reference:

Section 6, Reporting and Alarm Functions, Demand Functions

SG-EMAIL Command
Purpose:

Read/Enter email logic

Syntax:

SG-EMAIL[#[={email logic}]] where #=1-7

Example:

SG-EMAIL1=VO1*VO2 or SG-EMAIL5=50TPT+50TPPU

Reference:

Section 15, BESTNet Communication, Unique ASCII Commands

SG-FREQ Command
Purpose:

Read/Enter power system Frequency

Syntax:

SG-FREQ[={freq(HZ)}]

Example:

SG-FREQ=60 or SG-FREQ=50

Reference:

Section 3, Input and Output Functions, Power System Inputs

SG-HOLD Command
Purpose:

Read/Program Output Hold operation

Syntax:

SG-HOLD[n][={1/0 hold ena}] where 1=TRUE, 0=FALSE

Example:

SG-HOLD or SG-HOLD1=1 or SG-HOLD2=0

Reference:

Section 3, Input and Output Functions, Outputs

SG-ID Command
Purpose:

Read/Set relay ID and station ID used in reports

Syntax:

SG-ID[={relayID(up to 30 char)},{StationID(up to 30 char)}]

Example:

SG-ID=448,SUBSTATION3 or SG-ID=GEN3, POWERPOINT_SUBSTATION

Reference:

Section 14, BESTCOMS Software, Setting the Relay

9376700990 Rev M

BE1-700 ASCII Command Interface

11-15