Basler Electric BE1-700 User Manual

Page 190

Advertising
background image

Output

Purpose

Output Description

Label

State Labels

VO8

None

VO8

TRUE

FALSE

BESTlogic Expression: VO8=0

VO9

None

VO9

TRUE

FALSE

BESTlogic Expression: VO9=0

VO10

None

VO10

TRUE

FALSE

BESTlogic Expression: VO10=0

VO11

Protective Trip Expression TRUE when any 50, 150,51 or 151

element times out (trip).

PROT_

TRIP

TRIP

NORMAL

BESTlogic Expression: VO11=50TPT+50TNT+50TQT+150TPT+150TNT+150TQT+51PT+51NT+51QT +151NT

VO12

Protection Picked Up
Expression

TRUE when any 50, 150,51 or 151
element picks up.

PROT_PU

PU

NORMAL

BESTlogic Expression: VO12=50TPPU+50TNPU+50TQPU+150TPPU 150TNPU+150TQPU+51PPU
+51NPU+51QPU+151NPU

VO13

Alarm Mask 21

VO13

TRUE

FALSE

BESTlogic Expression: VO13=0

VO14

Alarm Mask 22

VO14

TRUE

FALSE

BESTlogic Expression: VO14=0

VO15

Alarm Mask 23

VO15

TRUE

FALSE

BESTlogic Expression: VO15=0

Table 8-5. 700C-5051-A-BE (Basic OC) Logic Settings and Equations

SL-N=700C-5051-A-BE
SL-50TP=1,0; SL-50TN=1,0; SL-50TQ=1,0
SL-150TP=0,0; SL-150TN=0,0; SL-150TQ=0,0
SL-51P=1,0
SL-51N=1,0
SL-51Q=1,0
SL-151N=0,0

8-8

BE1-700 Application

9376700990 Rev M