Basler Electric BE1-700 User Manual

Page 67

Advertising
background image

Table 4-6. BESTlogic Settings for 50TQ/150TQ Instantaneous Overcurrent Protection

Function

Range/Purpose

Default

Mode

0 = Disabled
1 = Enabled

1

BLK

Logic expression that disables function when TRUE.

0

Operating Settings for Instantaneous Overcurrent Protection

Operating settings for the 50T functions consist of Pickup and Time delay values. The Pickup value
determines the level of current required for the element to start timing toward a trip. Time delays can be
set in milliseconds, seconds, or cycles. The default is milliseconds if no unit of measure is specified.
Minimum timing resolution is to the nearest one-quarter cycle. A time delay setting of zero makes the
element instantaneous with no intentional time delay.

Operating settings are made using BESTCOMS. Figure 4-8 illustrates the BESTCOMS screen used to
select operational settings for the 50T elements. To open the BESTlogic Function Element screen, select
Overcurrent Protection from the Screens pull-down menu. Then select the 50T tab. Alternately, settings
may be made using S<g>-50T ASCII command or through HMI Screens 5.x.6.1 - 5.x.6.6 where x
represents 1 (Setting Group 0) or 2 (Setting Group 1).

The default unit of measure for the Pickup setting is secondary amps. Primary amps (Pri Amps), per unit
amps (Per U Amps), and percent amps (% Amps) can also be selected as the pickup setting unit of
measure. The unit of measure for the Time setting that represents the element's time delay defaults to
milliseconds. It is also selectable for seconds, minutes, and cycles.

If time delay settings are made in cycles, they are converted to seconds or milliseconds (per the nominal
frequency setting stored in EEPROM) before being stored and rounded to the nearest whole millisecond.
See Section 3, Input and Output Functions, Power System Inputs, Current Measurement, for more
information about this setting. If the nominal frequency setting is being changed from the default (60
hertz) and time delay settings are being set in cycles, the frequency setting should be entered and saved
before making any time delay settings changes.

Beside the Logic pull-down menu is a pull-down menu labeled Settings. The Settings menu is used to
select the setting group that the element's settings apply to.

Table 4-7 summarizes the operating settings for Instantaneous Overcurrent Protection.

NOTE

If the BE1-700 has 5 ampere phase inputs and a 1 ampere independent ground
input, the valid pickup setting range of the neutral overcurrent functions will
depend on the logic mode setting which designates whether the three-phase
residual or the independent ground input is to be monitored. If changing logic
schemes or settings causes a neutral overcurrent setting to be OUT OF RANGE,
the out of range setting will be forced in-range by multiplying or dividing the
current setting by 5.

9376700990 Rev M

BE1-700 Protection and Control

4-11

Advertising
This manual is related to the following products: